Specifications

63
GUIDE SPECIFICATIONS 7-46 kW DX units
Master unit fail safe mode allows slave units to revert their self control mode
T. No Water Flow Alarm - Unit shall be furnished with a NEMA 1 ow switch for eld mounting into the chilled water piping to
the unit. Upon a loss of water ow the unit control panel shall indicate “No Water Flow” and alarm shall sound.
U. Cable Type Water Detection Sensor - Units shall be provided with cable type water detection system designed to detect the
presence of water anywhere along the cable. Cable shall be mounted on the oor under the unit. Suf cient length of cable shall
be supplied to completely surround the perimeter of the unit so that water coming from anywhere within the unit will not escape
detection. The water detector shall become an integral part of the microprocessor panel and shall display “WATER DETECTED
IN UNDER FLOOR AREA” message and activate an audible alarm when the sensor is activated.
V. Discharge Plenum - Up ow units shall be equipped with an 18” tall discharge plenum with factory installed double de ection
front discharge grille. Plenum shall be constructed of minimum 18 gauge steel, lined with 1” 1.5 pound per cubic foot insulation
and painted to match the cabinet of the computer room air conditioning unit.
a. Discharge Plenum Side Discharge Grilles: Provide discharge grilles on ___ right side and ___ left side.
b. Extended Return Air Plenum: Down ow units shall be equipped with a four-sided inlet plenum on the return to extend
the return air opening of the unit. Plenums shall be of suf cient height to penetrate the lay-in ceiling. If lay-in ceiling is
not used plenum height shall suf cient to extend the return air opening to within 10” of the deck above or 6 feet which-
ever is shorter.
Plenum shall not be insulated, constructed of minimum 18 gauge steel and painted to match the color of the unit on which it is
mounted
W. Hot Water Reheat - Reheat will be provided by hot water coil with 1/2” copper tubes and aluminum ns rated for a maximum
working pressure of 300 PSI. Reheat circuit shall include a factory mounted 2-way hot water valve for temperature control. Coil,
control valve and controls as required for a functioning system shall be factory mounted.
X. Steam Reheat - Reheat will be provided by steam coil with 1/2” copper tubes and aluminum ns rated for a maximum work-
ing pressure of 300 PSI. Reheat circuit shall include a factory mounted 2-way steam valve rated at 20 psi close off pressure for
temperature control. Coil, control valve and controls as required for a functioning system shall be factory mounted. Steam strainer
and trap are required and shall be furnished and piped by the installing contractor.
1.11 WARRANTY
A. All parts in the unit shall be warranted to be free from defects in material or workmanship for Eighteen (18) months, from date
of shipment. Parts that fail during this period shall be repaired or a new part supplied by the manufacturer at no cost to the owner.
B. Manufacturers warranty shall be for parts only. Labor is not included.
C. (Optional) Extended Compressor Warranty – In addition to the manufacturers standard compressor warranty, the compres-
sors shall be provided with an extended warranty for a period of Forty-Two (42) months or a total of Five (5) years. The warranty
shall be for the replacement of compressors only (labor is not included).