Specifications
59
 GUIDE SPECIFICATIONS 7-46 kW DX units
1.08 WATER SENSOR
Units shall be provided with one (1) water sensor. The solid state water sensor shall be mounted under the unit to sense the pres-
ence of water. The sensor shall be connected to the microprocessor panel and activate an audible alarm. The water detector shall 
become an integral part of the microprocessor panel and shall display “WATER DETECTED IN UNDER FLOOR AREA” mes-
sage when the sensor is activated.
1.09 CONTROL PANEL
A.  The environmental control system shall be furnished with a microprocessor based Data Alarm Processor-III (DAP-III) 
panel. The panel shall include unit switching functions and display normal functions and service diagnostics on a 2 row, 80 
character backlit liquid crystal display (LCD) in a clear vernacular format. The panel shall allow recall and display of the high 
and low temperature for the last 24 hours, high and low humidity for the last 24 hours, current percent of capacity and average 
percent of capacity for the last hour of operation for cool 1, reheat, humidifi cation, dehumidifi cation, component runtimes for fan 
motor(s), reheat, humidifi cation and dehumidifi cation. Programming shall have multilevel password access to prevent unauthor-
ized access. Programming shall be accomplished entirely from the front of the unit without the need to access, set or program 
switches inside the unit (front door of the unit does not need to be opened). Programmable functions shall be entered on fl ash 
memory to ensure program retention should power fail. The historical database shall be maintained by battery backup. Multiple 
messages shall be displayed by automatically scrolling from each message to the next. Alarm conditions shall be displayed by au-
tomatically scrolling from each message to the next. Alarm conditions, in addition to being displayed, shall enunciate an audible 
alarm. A summary relay shall be available for remote alarms. Additional test or service terminal shall not be required for any 
functions. The control shall include temperature anticipation, moisture level humidity control and automatic fl ush cycles.
An alarm condition shall continue to be displayed until the malfunction is corrected. Multiple alarms shall be displayed sequen-
tially in order of occurrence and only those alarms, which have not been acknowledged, shall continue to sound an audible alarm. 
The Data alarm Processor-III panel shall perform an automatic self-test on system start-up. A user accessible diagnostic program 
shall aid in system component trouble shooting by displaying on the unit LCD screen the name of the controlled item, output relay 
number, terminal plug and pin number for each controlled item.
B. The following automatic control functions shall be included:
Selectable Control Type  Compressor Short Cycle
Selectable Water Under Floor Alarm Action  Automatic Reheat Element Rotation
Start Time Delay  Automatic or Manual Restart
Temperature Anticipation  Humidity Anticipation     
Dehumidifi cation Lockout  Sequential Load Activation
Energy Saver (Glycol Operation)*  Energy Saver Coil Flush Cycle*
Auxiliary Chilled Water Operation*  Chilled Water Coil Flush Cycle*
Hot Water Coil Flush Cycle*
C. The following conditions, data and normal functions shall be monitored and displayed:
Temperature Setpoint  Humidity Setpoint
Current Temperature  Current Humidity
Cooling 1  Dehumidifi cation
Reheat 1, 2, 3  Humidifi cation
Current Percent of Capacity Utilized  Current Discharge Temperature*
D. The following switching and control functions shall be included:
System On/Off Switch  Menu Selection Buttons
Menu Exit Button  Select Buttons
Alarm Silence Button  Program Set Button
Manual Override for:
  Cool 1, Heat 1, Humidifi cation










