Specifications
58
 GUIDE SPECIFICATIONS 7-46 kW DX units
type with complete overload protection on all three power lines, internal thermostats for winding protection, crankcase heater, 
sight-glass, condensers with sub-cooling and 2-way water regulating valve for head pressure control. The circuits shall contain 
high and low pressure safety switches. The high and low-pressure safety switches shall be installed with Shraeder type fi ttings 
with valve core.
The doors shall be painted to match or contrast with other room equipment.
Each system shall include a low profi le, slow speed, direct drive propeller fan type air cooled fl uid cooler. Air discharge shall 
be vertical to prevent wind from blowing through the coil at low ambient temperatures. The fl uid cooler shall be constructed of 
aluminum and contain a 1/2” O.D. rifl ed copper tube coil with corrugated aluminum fi ns for maximum heat transfer. The fan mo-
tors shall have cycling control provided on fl uid coolers with multiple fan motors. The fl uid cooler shall include surge tank and 
fi ll valve, pump contactor, and fan cycling controls with integral factory wired and tested control panel. The fl uid cooler shall be 
manufactured by the same manufacturer as the indoor unit.
1.04  DIRECT DRIVE PLENUM FAN SECTION
A.  The supply air fan shall be single width, single inlet plenum fan with backward inclined aluminum blades. Fan wheel 
shall be directly connected to its motor for greater effi ciency. Fan/motor assembly shall be statically and dynamically balanced for 
quiet, vibration-free operation and shall have a minimum L10 life of 60,000 hours. Fan shall be maintenance free throughout its 
operating life. 
B.  The fan motor shall be electronically commutated (EC) synchronous DC motor and shall meet the NEMA Premium 
standard. The EC motor shall have soft start capability and shall be controlled via the keypad on the unit mounted controller or by 
a 4 to 20 mili-amp control signal sent directly to the analog input on the motor. The fan shall be mounted within the unit and fully 
enclosed in an integral plenum to allow effi cient operation on raised fl oors with 12 or more inches of clearance under the fl oor. 
C. Belt drive fans with variable frequency drives are not considered equal or acceptable.
1.05 FILTER CHAMBER
The fi lter chamber shall be an integral part of the system, designed within the frame and cabinet. The fi lters shall be four inch 
(4”) deep pleated design, rated not less than 30% effi cient (based on ASHRAE Std. 52-76).
1.06 ELECTRIC REHEAT
The reheat shall be of the fi nned enclosed, sheath type, fabricated of stainless steel core sheath with plated fi ns to withstand moist 
conditions. The reheat shall be installed on the air discharge side of the cooling coil. The total kW shall be ___ to operate on a 
supply of ____ volts.
1.07 HUMIDIFIER
The unit shall be provided with steam generator type humidifi er. The steam generating humidifi er shall be of the self-contained 
disposable cylinder type with electronic controls. The capacity shall be adjustable from 10 to 30 pounds per hour. Power con-
sumption at 10 pounds per hour shall be 3.4 kW or less. The humidifi er shall discharge pure steam with no material dust carry-
over and have a self-regulating automatic fl ush cycle. Cylinders shall be disposable not requiring cleaning or maintenance. The 
humidifi er fi ll level, water conductivity and fl ush rate shall automatically adapt, both in frequency and duration, to variations in 
the incoming water.