GUIDE SPECIFICATIONS 7-46 kW DX units
Computer Room Air Conditioning Units
(Floor Mounted, Direct Expansion, 7 to 46 kW)
1.01 GENERAL
A. The environmental control units shall be provided with a high sensible cooling system, factory assembled, piped, wired,
and run tested prior to shipment and designed for either upfl ow or downfl ow air delivery as detailed on the project plans and
schedule.
B. The system shall be designed for draw through air arrangement to insure even air distribution to the entire face of the
coil.
C. Units shall be ETL or UL listed.
1.02 CABINET and FRAME
A. The frame shall be constructed of 14 gauge welded tubular steel and coated with a heavy corrosion inhibiting fi nish for
long life. The unit shall have complete front and side access by means of steel doors with heavy-duty hinges. All doors shall be
easily removable via lift-off hinges for easier service access. Doors shall be manufactured of minimum 18-gauge steel for superior
sound attenuation and shall be lined with one-inch thick, 1-1/2-pound density, fi berglass insulation. Each door shall be provided
with sure close latches and a polyurethane gasket to prevent air leakage.
B. The unit shall be painted the color selected from the manufacturer’s standard color chart.
1.03 REFRIGERATION CIRCUIT
A. Air Cooled with Remote Outdoor Condenser - The refrigeration system shall be split type with an indoor evaporator section
and remote outdoor condenser.
The indoor evaporator section shall include the cooling coil, compressors, humidifi er, reheat, fi lters, and controls. The cooling
coil shall be in a cross circuited or interlaced “A” frame arrangement to allow maximum coil surface in a small cabinet. The large
faced coil area shall be constructed with 1/2” O.D. rifl ed copper tube with 12 fi ns per inch of corrugated aluminum for maximum
heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valve shall be of the adjustable
thermostatic type with external equalization. The compressor shall be of the hermetic scroll with complete overload protection on
all three power lines, internal thermostat for winding protection, crankcase heater, sight-glass, and low pressure override timer for
positive starting at low temperatures. The circuit shall contain high and low pressure safety switches. The high and low pressure
safety switches shall be installed with Shraeder type fi ttings with valve core.
The doors shall be painted to match or contrast with other room equipment.
Each system shall include a low profi le, slow speed, direct drive propeller fan type air cooled condenser. The air discharge
shall be vertical to minimize the effects of wind blowing through the coil at low ambient temperatures. The condenser shall be
constructed of stainless steel. The condenser shall contain a 1/2” O.D. rifl ed copper tube coil with corrugated aluminum fi ns for
maximum heat transfer. The condenser shall have fan speed control with transducers to modulate the speed of the fi rst condenser
fan motor and provide positive start-up and operation at ambient temperatures to -20° F. Condensers with more than one fan shall
utilize a pressure control on the second fan. Condensers with additional condenser fan motors are to be controlled by ambient
thermostats. All controls including the fan speed controller shall be factory mounted in the air cooled condenser in an integral
factory wired and tested control panel. The air cooled condenser shall be manufactured by the manufacturer of the indoor unit.
B. Air Cooled with Floor Mounted Indoor Condenser - The refrigeration system shall be split type with an indoor evaporator sec-
tion and fl oor mounted indoor condenser section.
The indoor evaporator section shall include the cooling coil, compressors, humidifi er, reheat, fi lters, and controls. The cooling