Specifications

45
ENERGY SAVER: Performance data at OPTIONAL air ow
R-410A
gForce GT also available in R-407C. Data in a separate brochure.
Based on 45° F entering uid temperature with 40% glycol solution - capacity in Btu/hr.
MODEL NUMBER GT*D/U007 GT*D/U011 GT*D/U014 GT*D/U018 GT*D/U028 GT*D/U035 GT*D/U046
CAPACITY in Btu/hr - gross
75° F DB/62.5° F WB Total 26,000 35,200 52,300 62,800 N/A N/A N/A
50% RH Sensible 22,900 32,200 45,700 55,500 N/A N/A N/A
72° F DB/62.5° F WB Total 22,700 30,900 45,500 54,700 N/A N/A N/A
50% RH Sensible 21,300 29,800 42,400 51,500 N/A N/A N/A
Rows of coils 4 4 4 4 - - -
GPM 7.0 10.5 14.0 17.5 - - -
Pressure drop - PSI 4.6 10.1 9.2 14.6 - - -
FAN SECTION
Air ow - CFM 1,000 1,500 2,000 2,500 - - -
Number of fans 1 1 1 1 - - -
Standard fax - diameter (mm) 450 450 450 500 - - -
Fan motor - kW/HP
External static pressure (E.S.P.) - inches of W.G. 1/1.4 1/1.4 1/1.4 2.8/3.7 - - -
Maximum E.S.P. 1.5 1.5 1.0 1.5 - - -
Next size fan - diameter (mm) N/A N/A 500 500 - - -
Fan motor - kW/HP - - 2.8/3.7 2.8/3.7 - - -
Maximum E.S.P. - - 1.5 1.5 - - -
ELECTRICAL SECTION Standard Fan
Electrical data based on STANDARD unit: electric reheat - YES, steam generator humidi er - YES, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 30/37/40 33/40/45 54/67/70 62/76/80 - - -
460/3/60 FLA/MCA/MOP 14/17/20 15/19/20 26/32/35 28/35/40 - - -
Electrical data based on: electric reheat - NO, steam generator humidi er - YES, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 30/37/40 33/40/45 37/46/50 45/54/70 - - -
460/3/60 FLA/MCA/MOP 14/17/20 15/19/25 19/23/40 21/25/40 - - -
Electrical data based on: electric reheat - YES, steam generator humidi er - NO, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 30/37/40 33/40/45 54/67/70 62/76/80 - - -
460/3/60 FLA/MCA/MOP 14/17/20 15/19/20 26/32/35 28/35/40 - - -
Electrical data based on: electric reheat - NO, steam generator humidi er - NO, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 14/16/25 16/20/30 21/25/40 29/34/50 - - -
460/3/60 FLA/MCA/MOP 6.1/7.2/15 7.7/9.2/15 11/14/20 13/16/25 - - -
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps