Specifications
42
AUXILIARY CHILLED WATER: Performance data at STANDARD airfl ow
R-410A
gForce GT also available in R-407C. Data in a separate brochure.
Based on 45° F entering fl uid temperature - 0% glycol.
MODEL NUMBER GT*D/U007 GT*D/U011 GT*D/U014 GT*D/U018 GT*D/U028 GT*D/U035 GT*D/U046
CAPACITY in Btu/hr - gross
75° F DB/62.5° F WB Total 28,000 39,500 54,400 65,300 N/A N/A N/A
50% RH Sensible 21,700 31,200 42,400 51,600 N/A N/A N/A
72° F DB/62.5° F WB Total 23,800 33,600 46,200 55,500 N/A N/A N/A
50% RH Sensible 19,900 28,700 38,900 47,400 N/A N/A N/A
Rows of coils 4 4 4 4 - - -
GPM 7.0 10.5 14.0 17.5 - - -
Pressure drop in PSI 1.8 3.6 6.5 9.7 - - -
FAN SECTION
Airfl ow - CFM 800 1,200 1,600 2,000 - - -
Number of fans 1 1 1 1 - - -
Standard fax - diameter (mm) 450 450 450 450 - - -
Fan motor - kW/HP 1/1.4 1/1.4 1/1.4 1/1.4 - - -
External static pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5 - - -
Maximum E.S.P. 1.5 1.5 1.5 1.1 - - -
Next size fan - diameter (mm) N/A N/A N/A 500 - - -
Fan motor - kW/HP - - - 2.8/3.7 - - -
Minimum E.S.P. - - - 1.5 - - -
ELECTRICAL SECTION Standard Fan
Electrical data based on STANDARD unit: electric reheat - YES, steam generator humidifi er - YES, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 30/37/40 33/40/45 54/67/70 57/70/80 - - -
460/3/60 FLA/MCA/MOP 14/17/20 15/19/20 26/32/35 26/32/35 - - -
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 30/37/40 33/40/45 37/46/50 40/49/60 - - -
460/3/60 FLA/MCA/MOP 14/17/20 15/19/25 19/23/40 19/23/40 - - -
Electrical data based on: electric reheat - YES, steam generator humidifi er - NO, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 30/37/40 33/40/45 54/67/70 57/70/80 - - -
460/3/60 FLA/MCA/MOP 14/17/20 15/19/20 26/32/35 26/32/35 - - -
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 14/16/25 16/20/30 21/25/40 24/29/45 - - -
460/3/60 FLA/MCA/MOP 6.1/7.2/15 7.7/9.2/15 11/14/20 11/14/20 - - -
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps