Specifications
37
GLYCOL COOLED: Performance data at STANDARD airfl ow
MODEL NUMBER     GTGD/U007 GTGD/U011 GTGD/U014  GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046
  FLUID COOLER SELECTIONS
Fluid cooler at 95° F ambient    DAFC-06 DAFC-06 DAFC-06 DAFC-07  - - -
 208-230/1/60  FLA/MCA/MOP    4.6/5.8/15 4.6/5.8/15  4.6/5.8/15 4.6/5.8/15  -  -  -
 208-230/3/60  FLA/MCA/MOP    4.6/5.8/15 4.6/5.8/15  4.6/5.8/15 4.6/5.8/15  -  -  -
 460/3/60   FLA/MCA/MOP    2.3/2.9/15 2.3/2.9/15  2.3/2.9/15 2.3/2.9/15  -  -  -
Fluid cooler at 100° F ambient    DAFC-06 DAFC-06 DAFC-09 DAFC-15  - - -
 208-230/1/60  FLA/MCA/MOP  4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 9.2/10.4/15 - - -
 208-230/3/60  FLA/MCA/MOP  4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 9.2/10.4/15 - - -
 460/3/60   FLA/MCA/MOP    2.3/2.9/15 2.3/2.9/15  2.3/2.9/15 4.6/5.2/15  -  -  -
 CONDENSER WATER 
Requirements at maximum design water pressure of 150 psi (high pressure optional).
65° F entering fl uid temperature  GPM  2.6  3.9  5.2  6.5  -  -  -
        PD in PSI  0.9  1.9  0.9  1.2  -  -  -
75° F entering fl uid temperature  GPM  4.2  6.2  8.3  10.4  -  -  -
        PD in PSI  1.6  5.8  1.5  2.5  -  -  -
85° F entering fl uid temperature GPM 6.0 9.0 12.0 15.0  - - -
        PD in PSI  3.2  7.5  3.5  5.0  -  -  -
With fl uid cooler    GPM  7.0 10.5  14.0 17.5  -  -  -
        PD in PSI  4.0  8.2  4.4  6.5  -  -  -
  PUMP SELECTION     At design fl ow
Horsepower     3/4 3/4 1 1  - - -
  PUMP ELECTRICAL DATA
 208-230/1/60  FLA    4.8 4.8  5.8 5.8  -  -  -
 208-230/3/60  FLA    2.6 2.6  3.2 3.2  -  -  -
 460/3/60  FLA    1.3 1.3  1.6 1.6  -  -  -
Notes: Fluid coolers are not available in 575 volts.
   Fluid coolers are selected at sea level.
   Pump selection is based on total available head pressure of 80 feet of water.
FLA - Full load amps
R-410A
gForce GT also available in R-407C. Data in a separate brochure.