Specifications
36
GLYCOL COOLED: Performance data at STANDARD airfl ow
MODEL NUMBER     GTGD/U007 GTGD/U011 GTGD/U014  GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046
   ELECTRICAL SECTION   Next Size Fan
Electrical data based on: electric reheat - YES, steam generator humidifi er - YES, and NEXT SIZE FAN. 
 208-230/3/60  FLA/MCA/MOP  N/A N/A N/A 62/76/80 - - -
 460/3/60  FLA/MCA/MOP  N/A N/A N/A 28/35/40 - - -
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES, and NEXT SIZE FAN.
 208-230/3/60  FLA/MCA/MOP  N/A N/A N/A 45/54/70 - - -
 460/3/60  FLA/MCA/MOP  N/A N/A N/A 21/25/30 - - -
Electrical data based on: electric reheat - YES, steam generator humidifi er - NO, and NEXT SIZE FAN.
 208-230/3/60  FLA/MCA/MOP  N/A N/A N/A 62/76/80 - - -
 460/3/60  FLA/MCA/MOP  N/A N/A N/A 28/35/40 - - -
Electrical data based on: electric reheat -NO, steam generator humidifi er - NO, and NEXT SIZE FAN.
 208-230/3/60  FLA/MCA/MOP  N/A N/A N/A 29/34/50 - - -
 460/3/60  FLA/MCA/MOP  N/A N/A N/A 13/16/25 - - -
  COMPRESSOR  FLA - Full load amps
  208-230/3/60    10.4 13.1 17.6 20.5  -  -  -
  460/3/60    4.5 6.1 9.6 9.6  -  -  -
* * * The following section has no reference to column heading * * *
  NEXT LARGER FAN     FLA - Full load amps
Diameter/kW/HP  500/2.8/3.7
 208-230/3/60    8.2
 460/3/60    3.7
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
R-410A
gForce GT also available in R-407C. Data in a separate brochure.