Specifications
33
WATER COOLED: Performance data at OPTIONAL airfl ow
MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046
CONDENSER WATER
Requirements at maximum design water pressure of 150 psi (high pressure optional).
65° F entering fl uid temperature GPM 2.6 3.9 5.2 6.5 - - -
PD in PSI 0.9 1.9 0.9 1.2 - - -
75° F entering fl uid temperature GPM 4.2 6.2 8.3 10.4 - - -
PD in PSI 1.6 5.8 1.5 2.5 - - -
85° F entering fl uid temperature GPM 6.0 9.0 12.0 15.0 - - -
PD in PSI 3.2 7.5 3.5 5.0 - - -
With fl uid cooler GPM 7.0 10.5 14.0 17.5 - - -
PD in PSI 4.0 8.2 4.4 6.5 - - -
PUMP SELECTION At design fl ow
Horsepower 3/4 3/4 1 1 - - -
PUMP ELECTRICAL DATA
208-230/1/60 FLA 4.8 4.8 5.8 5.8 - - -
208-230/3/60 FLA 2.6 2.6 3.2 3.2 - - -
460/3/60 FLA 1.3 1.3 1.6 1.6 - - -
(Note: Pump selection is based on total available head pressure of 80 feet of water.)
FLA - Full Load Amps
R-410A
gForce GT also available in R-407C. Data in a separate brochure.