Specifications
32
WATER COOLED: Performance data at OPTIONAL airfl ow
MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046
ELECTRICAL SECTION Next Size Fan
Electrical data based on: electric reheat -YES, steam generator humidifi er - YES, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 59/72/80 62/76/80 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 28/35/40 28/35/40 N/A N/A N/A
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 42/51/60 45/54/70 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 21/25/30 21/25/30 N/A N/A N/A
Electrical data based on: electric reheat - YES, steam generator humidifi er - NO, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 59/72/80 62/76/80 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 28/35/40 28/35/40 N/A N/A N/A
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 26/30/45 29/34/50 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 13/16/25 13/16/25 N/A N/A N/A
COMPRESSOR FLA - Full load amps
208-230/3/60 10.4 13.1 17.6 20.5 - - -
460/3/60 4.5 6.1 9.6 9.6 - - -
* * * The following section has no reference to column heading * * *
NEXT LARGER FAN FLA - Full load amps
Diameter/kW/HP 500/2.8/3.7
208-230/3/60 8.2
460/3/60 3.7
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
R-410A
gForce GT also available in R-407C. Data in a separate brochure.