Specifications
26
MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046
CAPACITY in Btu/hr - gross
80° DB/67° WB Total 30,000 44,700 60,300 70,200 N/A N/A N/A
50% RH Sensible 21,400 31,700 43,400 52,600 N/A N/A N/A
75° DB/62.5° WB Total 27,700 41,300 55,700 65,200 N/A N/A N/A
50% RH Sensible 20,700 30,600 41,900 50,800 N/A N/A N/A
75° DB/61° WB Total 26,800 40,000 53,800 63,300 N/A N/A N/A
45% RH Sensible 21,900 32,500 44,400 54,200 N/A N/A N/A
72° DB/60° WB Total 26,400 39,300 53,000 62,300 N/A N/A N/A
50% RH Sensible 20,200 29,900 41,000 49,700 N/A N/A N/A
72° DB/58.6° WB Total 26,100 38,400 51,500 60,900 N/A N/A N/A
45% RH Sensible 21,500 31,600 43,200 52,800 N/A N/A N/A
FAN SECTION
Airfl ow - CFM 800 1,200 1,600 2,000 - - -
Number of fans 1 1 1 1 - - -
Standard fax - diameter (mm) 450 450 450 450 - - -
Fan motor - kW/HP 1/1.4 1/1.4 1/1.4 1/1.4 - - -
External static pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5 - - -
Maximum E.S.P. 1.5 1.5 1.5 1.3 - - -
Next size fan - diameter (mm) N/A N/A N/A 500 - - -
Fan motor - kW/HP - - - 2.8/3.7 - - -
Minimum E.S.P. - - - 1.5 - - -
COMPRESSORS
Type Scroll Scroll Scroll Scroll - - -
Quantity 1 1 1 1 - - -
Refrigerant type R-410A R-410A R-410A R-410A - - -
EVAPORATOR COIL
Face area - sq ft 4.2 4.2 6.25 6.25 - - -
Rows of coils 3 3 4 4 - - -
Face velocity - fpm 190 286 256 320 - - -
REHEAT SECTION
Electric Standard Standard Standard Standard - - -
kW 6 6 12 12 - - -
Capacity - Btu/hr 20,490 20,490 40,980 40,980 - - -
HUMIDIFIER SECTION
Steam generator Standard Standard Standard Standard - - -
kW 3.4 3.4 3.4 3.4 - - -
Capacity - lb/hr 10 10 10 10 - - -
WATER COOLED: Performance data at STANDARD airfl ow
R-410A
gForce GT also available in R-407C. Data in a separate brochure.