Specifications

24
AIR COOLED: Performance Data at OPTIONAL air ow with remote outdoor condensing unit
R-410A
gForce GT also available in R-407C. Data in a separate brochure.
MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046
ELECTRICAL Next Size Motor
Electrical data based on: electric reheat - YES, steam generator humidi er - YES, and NEXT LARGER FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 42/52/60 42/52/60 51/32/70 N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 19/24/25 19/24/25 23/29/30 26/32/35 N/A
Electrical data based on: electric reheat - NO, steam generator humidi er - YES, and NEXT LARGER FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 25/31/35 25/31/35 25/31/35 N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 11/14/15 11/14/15 12/15/20 14/18/20 N/A
Electrical data based on: electric reheat - YES, steam generator humidi er - NO, and NEXT LARGER FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 42/52/60 42/52/60 51/63/70 N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 19/24/25 19/24/25 23/29/30 26/32/35 N/A
Electrical data based on: electric reheat - NO, steam generator humidi er - NO, and NEXT LARGER FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 8.2/10/15 8.2/10/15 8.8/11/15 N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 3.7/4.6/15 3.7/4.6/15 4.3/5.4/15 6.7/8.4/15 N/A
COMPRESSOR FLA - Full load amps
208-230/3/60 10.4 13.1 17.6 20.5 30.1 33.3 51.3
460/3/60 4.5 6.1 9.6 9.6 16.7 17.9 23.1
* * * The following section has no reference to column heading * * *
NEXT LARGER FAN FLA - Full load amps
Diameter/kW/HP 500/2.8/3.7 560/3.0/4.0 560/5.0/6.7
208-230/3/60 8.2 8.8 N/A
460/3/60 3.7 4.3 6.7
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps