Specifications

23
MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046
FILTER SECTION
Quantity Size - inches Down ow 1-16x20x4 1-16x20x4 1-16x20x4 2-16x20x4 2-16x25x4 2-16x25x4 2-16x25x4
1-20x20x4 1-20x20x4 1-20x20x4 2-20x20x4 2-20x25x4 2-20x25x4 2-20x25x4
Up ow 1-16x25x4 1-16x25x4 1-16x25x4 2-16x25x4 1-20x25x4 1-20x25x4 1-20x25x4
1-20x25x4 1-20x25x4 1-20x25x4 2-20x25x4 2-16x25x4 2-16x25x4 2-16x25x4
Ef ciency - percent 30 30 30 30 30 30 30
(Note: Filter ef ciency based on ASHRAE Std. 52.1-1992.)
CONNECTION SIZES
Liquid line - O.D. Copper 1/2 1/2 1/2 1/2 5/8 5/8 5/8
Suction line - O.D. Copper 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate drain 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Humidi er supply 1/4 1/4 1/4 1/4 1/4 1/4 1/4
(Note: Refer to Operation and Maintenance manual for recommended pipe sizing between indoor section and condensing unit.)
ELECTRICAL Standard Fan
Electrical data based on STANDARD unit: electric reheat - YES, steam generator humidi er - YES, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 20/25/30 20/25/30 36/46/50 36/46/50 50/62/70 51/63/70 N/A
460/3/60 FLA/MCA/MOP 9.1/11/15 9.1/11/15 17/21/25 17/21/25 23/28/30 23/29/30 26/32/35
Electrical data based on: electric reheat - NO, steam generator humidi er - YES, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 19/24/25 19/24/25 19/24/25 19/24/25 25/31/35 25/31/35 N/A
460/3/60 FLA/MCA/MOP 9.0/11/15 9.0/11/15 9.0/11/15 9.0/11/15 11/14/15 12/15/20 14/18/20
Electrical data based on: electric reheat - YES, steam generator humidi er - NO, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 20/25/30 20/25/30 36/46/50 36/46/50 50/62/70 50/62/70 N/A
460/3/60 FLA/MCA/MOP 9.1/11/15 9.1/11/15 17/21/25 17/21/25 23/28/30 23/29/30 26/32/35
Electrical data based on: electric reheat - NO, steam generator humidi er - NO, and STANDARD FAN.
208-230/3/60 FLA/MCA/MOP 3.1/3.9/15 3.1/3.9/15 3.1/3.9/15 3.1/3.9/15 8.2/10/15 8.8/11/15 N/A
460/3/60 FLA/MCA/MOP 1.6/2.0/15 1.6/2.0/15 1.6/2.0/15 1.6/2.0/15 3.7/4.6/15 4.3/5.4/15 6.7/8.4/15
EVAPORATOR FAN MOTOR FLA - Full load amps
Diameter (mm)/ kW/HP 450/1.0/1.4 500/2.8/3.7 560/3.0/4.0 560/5.0/6.7
208-230/3/60 3.1 8.2 8.8 N/A
460/3/60 1.6 3.7 4.3 6.7
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
AIR COOLED: Performance data at OPTIONAL air ow with remote outdoor condensing unit
R-410A
gForce GT also available in R-407C. Data in a separate brochure.