Specifications
20
AIR COOLED: Performance data at STANDARD airfl ow with remote outdoor condensing unit
R-410A
gForce GT also available in R-407C. Data in a separate brochure.
MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046
ELECTRICAL SECTION Next Size Fan
Electrical data based on: electric reheat- YES, steam generator humidifi er YES, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A N/A 42/52/60 N/A N/A 51/63/70
460/3/60 FLA/MCA/MOP N/A N/A N/A 19/24/25 N/A N/A 23/29/30
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A N/A 25/31/35 N/A N/A 25/31/35
460/3/60 FLA/MCA/MOP N/A N/A N/A 11/14/15 N/A N/A 12/15/20
Electrical data based on: electric reheat - YES, steam generator humidifi er - NO, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A N/A 42/52/60 N/A N/A 51/63/70
460/3/60 FLA/MCA/MOP N/A N/A N/A 19/24/25 N/A N/A 23/29/30
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A N/A 8.2/10/15 N/A N/A 8.8/11/15
460/3/60 FLA/MCA/MOP N/A N/A N/A 3.7/4.6/15 N/A N/A 4.3/5.4/15
COMPRESSOR FLA - Full load amps
208-230/3/60 10.4 13.1 17.6 20.5 30.1 33.3 51.3
460/3/60 4.5 6.1 9.6 9.6 16.7 17.9 23.1
* * * The following section has no reference to column heading * * *
NEXT LARGER FAN FLA - Full load amps
Diameter/kW/HP 500/2.8/3.7 560/3.0/4.0
208-230/3/60 8.2 8.8
460/3/60 3.7 6.7
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps