Specifications

17
AIR COOLED: Performance data at OPTIONAL air ow with remote air cooled condenser
MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046
ELECTRICAL SECTION Next Size Fan
Electrical data based on: electric reheat -YES, steam generator humidi er - YES, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 59/72/80 62/76/80 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 28/35/40 28/35/40 N/A N/A N/A
Electrical data based on: electric reheat - NO, steam generator humidi er - YES, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 42/51/60 45/54/70 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 21/25/30 21/25/30 N/A N/A N/A
Electrical data based on: electric reheat - YES, steam generator humidi er - NO, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 59/72/80 62/76/80 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 28/35/40 28/35/40 N/A N/A N/A
Electrical data based on: electric reheat - NO, steam generator humidi er - NO, and NEXT SIZE FAN.
208-230/3/60 FLA/MCA/MOP N/A N/A 26/30/45 29/34/50 N/A N/A N/A
460/3/60 FLA/MCA/MOP N/A N/A 13/16/25 13/16/25 N/A N/A N/A
COMPRESSOR FLA - Full load amps
HP 2 3 4 5 - - -
208-230/3/60 10.4 13.1 17.6 20.5 - - -
460/3/60 4.5 6.1 9.6 9.6 - - -
NEXT SIZE FAN FLA - full load amps
Diameter (mm)/kW/HP 500/2.8/3.7
208-230/3/60 8.2
460/3/60 3.7
CONDENSER FLA - full load amps
Condenser selection at 95° F ambient DARC-03 DARC-03 DARC-05 DARC-05 - - -
Condenser selection at 100° F ambient DARC-03 DARC-03 DARC-05 DARC-06 - - -
Condenser selection at 105° F ambient DARC-03 DARC-05 DARC-06 DARC-07 - - -
(Note: Condensers are not available in 575 volts. Condensers are selected at sea level. Refer to page 63 for electrical data.)
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
R-410A
gForce GT also available in R-407C. Data in a separate brochure.