gForce GT R-410A Single Circuit Air Cooled, Water/Glycol Cooled 7 to 46 kW
… the pioneer and builder of the most complete line of precision cooling equipment Back in the late 1960’s and early 70’s with the advancement of the computer and computer rooms, precision environmental control equipment with high sensible cooling ratios became a necessity. Data Aire, a division of Supreme Aire, worked with leading computer facility engineers to develop one of the first down discharge air conditioning units for raised floor application.
Table of Contents Design features ........................................................................................................ 7 Control systems........................................................................................................ 8 Options ................................................................................................................... 10 Performance Data Air Cooled..............................................................................................
- GT IMPROVED PERFORMANCE and REDUCED MAINTENANCE MISSION CRITICAL COOLING gForce by Data Aire provides the most advanced features in mission critical cooling equipment available on the market today. These units are the most efficient and economical while complying with strict environmental requirements. Backward curved fans discharge air radially allowing for uniform static pressure across the raised floor.
INCREASED THERMODYNAMIC EFFICIENTIES R-407C is a blend of three refrigerants and has characteristics similar to R-22. R-410A is a blend of two refrigerants and has a higher volumetric cooling capacity but operates at higher pressures than either R-22 or R-407C. The choice of the environmentally friendly refrigerant is yours. gForce’s design incorporates rifled tubing cooling coils. Rifle tubing is similar to borings in a gun barrel which forces the bullet to rotate.
DESIGN FEATURES FRAME AND CABINET bility of refrigerant or oil leaking into the controlled space or environment. Scroll compressors also bring a combination of reliability, efficiency, and improved system sound performance.
CONTROL SYSTEM DATA ALARM PROCESSOR-III The Data Alarm Processor-III (DAP™ III) offers the definitive answer for precision environmental control. The DAP-III control system not only controls and monitors temperature, humidity, airflow and cleanliness, it provides component run times, alarm history and an automatic self-test of the microprocessor on system start-up. All messages are presented in a clear vernacular format and sequentially displayed on a backlit, liquid crystal display (LCD).
CONTROL SYSTEM, continued PROTECTIVE and SAFETY FEATURES Metal shell enclosure with sealed front control panel Opto-coupler signal inputs Heavy ground planes and power foils Switching power supply Watch dog timer Protected 24VAC power input Isolation transformer Fuses on all control boards CONDITIONS and DATA DISPLAYED Current percent of capacity utilized Current temperature Current humidity Current discharge air temperature* Current chilled water temperature* Cooling stages Reheat stages Chilled water
OPTIONS Energy Saver Coil - The Data Aire Energy Saver Coil is built into the system to provide total required capacity. Whenever the incoming water/glycol temperature is below 45° F/7.2° C, Energy Saver cooling is available. Energy Saver mode operates in the following range: Return air setpoint plus deadband plus two degrees. The Energy Saver will operate providing there is a need for cooling. The valve will open at setpoint plus deadband.
OPTIONS, continued Site Monitoring Devices the evaporator under full load will maintain pressure on the leaving side of the hot gas bypass valve to keep the valve port closed.
AIR COOLED: Performance data at STANDARD AIRFLOW with remote air cooled condenser R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in kW/hr - gross 80° DB/67° WB 50% RH Total Sensible 26,700 20,100 39,700 29,700 53,900 40,900 62,500 49,600 N/A N/A N/A N/A N/A N/A 75° DB/62.
AIR COOLED: Performance data at STANDARD airflow with remote air cooled condenser R-410A gForce GT also available in R-407C. Data in a separate brochure.
AIR COOLED: Performance data at STANDARD airflow with remote air cooled condenser R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 ELECTRICAL SECTION GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 - - - - - - 62/76/80 28/35/40 - - - Next Size Fan Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE FAN.
AIR COOLED: Performance data at OPTIONAL airflow with remote air cooled condenser R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in Btu/hr - gross 80° DB/67° WB 50% RH Total Sensible 27,900 22,800 41,300 33,500 55,800 46,300 64,800 56,800 N/A N/A N/A N/A N/A N/A 75° DB/62.
AIR COOLED: Performance Data at OPTIONAL airflow with remote air cooled condenser R-410A gForce GT also available in R-407C. Data in a separate brochure.
AIR COOLED: Performance data at OPTIONAL airflow with remote air cooled condenser R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 ELECTRICAL SECTION GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 62/76/80 28/35/40 N/A N/A N/A N/A N/A N/A Next Size Fan Electrical data based on: electric reheat -YES, steam generator humidifier - YES, and NEXT SIZE FAN.
AIR COOLED: Performance data at STANDARD airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in Btu/hr - gross 80° DB/67° WB 50% RH Total Sensible 26,700 20,100 39,700 29,700 53,900 40,900 62,500 49,600 110,100 85,500 132,600 102,200 163,500 122,100 75° DB/62.
AIR COOLED: Performance data at STANDARD airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 1-16x20x4 1-20x20x4 1-16x20x4 1-20x20x4 1-16x20x4 1-20x20x4 2-16x20x4 2-20x20x4 2-16x25x4 2-20x25x4 2-16x25x4 2-20x25x4 2-16x25x4 2-20x25x4 1-16x25x4 1-20x25x4 Efficiency - percent 30 (Note: Filter efficiency based on ASHRAE Std. 52.1-1992.
AIR COOLED: Performance data at STANDARD airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 ELECTRICAL SECTION GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 N/A N/A N/A N/A 51/63/70 23/29/30 N/A N/A N/A N/A 25/31/35 12/15/20 42/52/60 19/24/25 N/A N/A N/A N/A 51/63/70 23/29/30 Next Size Fan Electrical data based on: electric reheat- YES, steam generator humidifier YES, and NEXT SIZE FAN.
AIR COOLED: Performance data at STANDARD airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure.
AIR COOLED: Performance data at OPTIONAL airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 CAPACITY in Btu/hr - gross 80° DB/67° WB 50% RH Total Sensible 27,900 22,800 41,300 33,500 55,800 46,300 64,800 56,800 112,600 95,200 136,700 115,800 170,000 137,100 75° DB/62.
AIR COOLED: Performance data at OPTIONAL airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure.
AIR COOLED: Performance Data at OPTIONAL airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTAD/U007 ELECTRICAL GTAD/U011 GTAD/U014 GTAD/U018 GTAD/U028 GTAD/U035 GTAD/U046 51/32/70 23/29/30 N/A 26/32/35 N/A N/A 25/31/35 12/15/20 N/A 14/18/20 N/A N/A 51/63/70 23/29/30 N/A 26/32/35 N/A N/A Next Size Motor Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT LARGER FAN.
AIR COOLED: Performance data at OPTIONAL airflow with remote outdoor condensing unit R-410A gForce GT also available in R-407C. Data in a separate brochure.
WATER COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CAPACITY in Btu/hr - gross 80° DB/67° WB 50% RH Total Sensible 30,000 21,400 44,700 31,700 60,300 43,400 70,200 52,600 N/A N/A N/A N/A N/A N/A 75° DB/62.
WATER COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 FILTER SECTION Quantity Size - inches 2 16x20x4 20x20x4 Upflow 16x25x4 20x25x4 Efficiency - percentage 30 (Note: Filter efficiency based on ASHRAE Std. 52.1-1992.
WATER COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 ELECTRICAL SECTION Next Size Fan Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE FAN.
WATER COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CONDENSER WATER Requirements at maximum design water pressure of 150 psi (high pressure optional). 65° F entering fluid temperature GPM PD in PSI 2.6 0.9 3.9 1.9 5.2 0.9 6.5 1.2 - - - 75° F entering fluid temperature GPM PD in PSI 4.2 1.6 6.2 5.8 8.3 1.5 10.4 2.
WATER COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CAPACITY in Btu/hr - gross 80° DB/67° WB 50% RH Total Sensible 31,400 24,200 46,300 35,500 62,800 49,100 73,100 59,700 N/A N/A N/A N/A N/A N/A 75° DB/62.
WATER COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 FILTER SECTION Quantity Size - inches 2 16x20x4 20x20x4 Upflow 16x25x4 20x25x4 Efficiency - percentage 30 (Note: Filter efficiency based on ASHRAE Std. 52.1-1992.
WATER COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 ELECTRICAL SECTION Next Size Fan Electrical data based on: electric reheat -YES, steam generator humidifier - YES, and NEXT SIZE FAN.
WATER COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTWD/U007 GTWD/U011 GTWD/U014 GTWD/U018 GTWD/U028 GTWD/U035 GTWD/U046 CONDENSER WATER Requirements at maximum design water pressure of 150 psi (high pressure optional). 65° F entering fluid temperature GPM PD in PSI 2.6 0.9 3.9 1.9 5.2 0.9 6.5 1.2 - - - 75° F entering fluid temperature GPM PD in PSI 4.2 1.6 6.2 5.8 8.3 1.5 10.4 2.
GLYCOL COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 CAPACITY in Btu/hr - gross 80° DB/67° WB 50% RH Total Sensible 25,800 19,700 38,500 29,200 52,100 40,200 61,200 49,100 N/A N/A N/A N/A N/A N/A 75° DB/62.
GLYCOL COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FILTER SECTION Quantity Size - inches 2 16x20x4 20x20x4 Upflow 16x25x4 20x25x4 Efficiency - percentage 30 (Note: Filter efficiency based on ASHRAE Std. 52.1-1992.
GLYCOL COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 ELECTRICAL SECTION GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 Next Size Fan Electrical data based on: electric reheat - YES, steam generator humidifier - YES, and NEXT SIZE FAN.
GLYCOL COOLED: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FLUID COOLER SELECTIONS Fluid cooler at 95° F ambient 208-230/1/60 208-230/3/60 460/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP Fluid cooler at 100° F ambient 208-230/1/60 208-230/3/60 460/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP DAFC-06 DAFC-06 DAFC-06 DAFC-07 - - - 4.6/5.8/15 4.6/5.8/15 2.
GLYCOL COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure.
GLYCOL COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FILTER SECTION Quantity Size - inches 2 16x20x4 20x20x4 Upflow 16x25x4 20x25x4 Efficiency - percentage 30 (Note: Filter efficiency based on ASHRAE Std. 52.1-1992.
GLYCOL COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 ELECTRICAL SECTION GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 Next Size Fan Electrical data based on: electric reheat -YES, steam generator humidifier - YES, and NEXT SIZE FAN.
GLYCOL COOLED: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. MODEL NUMBER GTGD/U007 GTGD/U011 GTGD/U014 GTGD/U018 GTGD/U028 GTGD/U035 GTGD/U046 FLUID COOLER SELECTIONS Fluid cooler at 95° F ambient 208-230/1/60 FLA/MCA/MOP 208-230/3/60 FLA/MCA/MOP 460/3/60 FLA/MCA/MOP DAFC-06 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DAFC-06 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DAFC-06 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DAFC-07 4.6/5.8/15 4.6/5.8/15 2.3/2.
AUXILIARY CHILLED WATER: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. Based on 45° F entering fluid temperature - 0% glycol. MODEL NUMBER GT*D/U007 GT*D/U011 GT*D/U014 GT*D/U018 GT*D/U028 GT*D/U035 GT*D/U046 75° F DB/62.5° F WB Total 50% RH Sensible 28,000 21,700 39,500 31,200 54,400 42,400 65,300 51,600 N/A N/A N/A N/A N/A N/A 72° F DB/62.
AUXILIARY CHILLED WATER: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. Based on 45° F entering fluid temperature - 0% glycol. MODEL NUMBER GT*D/U007 GT*D/U011 GT*D/U014 GT*D/U018 GT*D/U028 GT*D/U035 GT*D/U046 75° F DB/62.5° F WB Total 50% RH Sensible 31,900 25,600 44,700 36,700 61,800 50,000 73,900 47,400 N/A N/A N/A N/A N/A N/A 72° F DB/62.
ENERGY SAVER: Performance data at STANDARD airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. Based on 45° F entering fluid temperature with 40% glycol solution - capacity in Btu/hr. MODEL NUMBER GT*D/U007 GT*D/U011 GT*D/U014 GT*D/U018 GT*D/U028 GT*D/U035 GT*D/U046 75° F DB/62.5° F WB Total 50% RH Sensible 23,300 19,600 31,700 27,600 46,800 39,000 56,300 47,500 N/A N/A N/A N/A N/A N/A 72° F DB/62.
ENERGY SAVER: Performance data at OPTIONAL airflow R-410A gForce GT also available in R-407C. Data in a separate brochure. Based on 45° F entering fluid temperature with 40% glycol solution - capacity in Btu/hr. MODEL NUMBER GT*D/U007 GT*D/U011 GT*D/U014 GT*D/U018 GT*D/U028 GT*D/U035 GT*D/U046 75° F DB/62.5° F WB Total 50% RH Sensible 26,000 22,900 35,200 32,200 52,300 45,700 62,800 55,500 N/A N/A N/A N/A N/A N/A 72° F DB/62.
gForce GT DX Downflow 7, 11, 14 and 18 kW 46
gForce GT DX Upflow 7, 11, 14 and 18 kW 47
gForce GT DX Downflow 28, 35 and 46 kW using Condensing units 48
gForce GT DX Upflow 28, 35 and 46 kW using Condensing units 49
DATA TEMP Air Cooled Condensers, DARC 03 and 05, single circuit 50
DATA TEMP Air Cooled Condensers, DARC 06-21, single circuit 51
DATA TEMP Air Cooled Condensers, DARC 06-21, single circuit 52
DATA TEMP Fluid Coolers, DAFC 06-30 53
DATA TEMP Fluid Coolers, DAFC 06-30 54
Standard Condenser and Fluid Cooler Electrical Data Standard Condenser Electrical Data Model 208/1/60 208/3/60 460/3/60 FLA/MCA/MOP FLA/MCA/MOP FLA/MCA/MOP DARC 03 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DARC 05 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DARC & DAFC 06 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DARC & DAFC 07 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DARC & DAFC 09 4.6/5.8/15 4.6/5.8/15 2.3/2.9/15 DARC & DAFC11 9.2/10.4/15 9.2/10.4/15 4.6/5.2/15 DARC & DAFC 15 9.2/10.4/15 9.2/10.4/15 4.6/5.
GUIDE SPECIFICATIONS 7-46 kW DX units Computer Room Air Conditioning Units (Floor Mounted, Direct Expansion, 7 to 46 kW) 1.01 GENERAL A. The environmental control units shall be provided with a high sensible cooling system, factory assembled, piped, wired, and run tested prior to shipment and designed for either upflow or downflow air delivery as detailed on the project plans and schedule. B. coil.
GUIDE SPECIFICATIONS 7-46 kW DX units coil shall be in a cross circuited or interlaced “A” frame arrangement to allow maximum coil surface in a small cabinet. The large faced coil area shall be constructed with 1/2” O.D. rifled copper tube with 12 fins per inch of corrugated aluminum for maximum heat transfer. Maximum face velocity shall be less than 500 feet per minute. The expansion valve shall be of the adjustable thermostatic type with external equalization.
GUIDE SPECIFICATIONS 7-46 kW DX units type with complete overload protection on all three power lines, internal thermostats for winding protection, crankcase heater, sight-glass, condensers with sub-cooling and 2-way water regulating valve for head pressure control. The circuits shall contain high and low pressure safety switches. The high and low-pressure safety switches shall be installed with Shraeder type fittings with valve core.
GUIDE SPECIFICATIONS 1.08 7-46 kW DX units WATER SENSOR Units shall be provided with one (1) water sensor. The solid state water sensor shall be mounted under the unit to sense the presence of water. The sensor shall be connected to the microprocessor panel and activate an audible alarm. The water detector shall become an integral part of the microprocessor panel and shall display “WATER DETECTED IN UNDER FLOOR AREA” message when the sensor is activated. 1.09 CONTROL PANEL A.
GUIDE SPECIFICATIONS 7-46 kW DX units E.
GUIDE SPECIFICATIONS 7-46 kW DX units The following protocols shall be supported: Modbus RTU, TCP/IP or ASCHII BACnet IP or MS/TP Johnson Metasys (N2) SNMP V1 or V2 LonTalk SNVT I. Building Management System Interface: Unit(s) shall be furnished with an interface card to communicate directly with the Building Automation System (BAS) through a RS-485, Ethernet or LonTalk port.
GUIDE SPECIFICATIONS 7-46 kW DX units for field installation and shall include sump, motor, and automatic control. The pumps shall be rated for 130 GPH @ 20 foot maximum head (40 GPH @ 20 feet with check valve). H. Tandem Scroll Compressors - Provide units with tandem hermetic scroll compressors with two-step modulation for stage control. Each circuit shall contain two scroll compressors.
GUIDE SPECIFICATIONS 7-46 kW DX units • Master unit fail safe mode allows slave units to revert their self control mode T. No Water Flow Alarm - Unit shall be furnished with a NEMA 1 flow switch for field mounting into the chilled water piping to the unit. Upon a loss of water flow the unit control panel shall indicate “No Water Flow” and alarm shall sound. U.