Installation manual
20 
VENTING  
MAXIMUM VERTICAL & HORIZONTAL 
COMBINATION VENTING  
 8” x 6-5/8” DECREASER 
VERTICAL & HORIZONTAL COMBINATION TERMINATIONS 
MAXIMUM VERTICAL & HORIZONTAL 
COMBINATION VENTING  
5” x 8”  
20ft. 
(6.10m) 
20ft. 
(6.10m) 
20ft. 
(6.10m) 
20ft. 
(6.10m) 
90° ELBOW 
TERMINATION CAP 
8” x 6-5/8” DECREASER 
6” (152mm) 
Figure 20b 
Figure 20a 
NOTE 
Page  19  has information  on  restrictor  installation  in  conjunction  with  venting  installation.  Page 29  has  information  on  
restrictor recommendations depending on burner flame appearance and instructions on installation after venting is completed. 
Horizontal sections require 1/4” (6mm) rise for every 12” (305mm) of travel. 
For each additional elbow used after first elbow, 3ft. (914mm) must be subtracted from maximum venting allowed. For each 45° elbow 
used, 1-1/2ft. (457mm) must be subtracted from maximum venting allowed. 
(2) 45° degree elbows may be used in place of (1) 90° elbow. 
IMPORTANT 
The horizontal vent heat shield must be installed when using a 90-degree elbow to horizontally position the vent system. 
Kozy Heat Wall Pass-thru, #800-WPT (4-1/2” (114mm) - 6-1/2” (165mm) wall thickness) or, 
#800-WPT2 (6-1/2” (165mm) - 12-1/2” (318mm) wall thickness), must be used on all 5” x 8” horizontal vent runs.  
If using 8” x 6-58” Decreaser, follow manufacturer’s instructions. 
CAUTION  This gas appliance must not be connected to or joined with any other chimney flue serving another appliance. 
90° ELBOW 
TERMINATION CAP 