Installation manual

19
VENTING
VERTICAL TERMINATIONS
MIN. / MAX. VERTICAL VENTING (5” x 8”)
MIN. / MAX. VERTICAL VENTING
(8” x 6-5/8” DECREASER)
RECOMMENDED:
Vertical terminations over 6ft. (1.82m): 1 restrictor
Maximum vertical terminations: 2 offset restrictors
RESTRICTOR INSTALLATION
MINIMUM: 4ft. (1.22m)
MAXIMUM: 40ft. (12.19m)
8” x 6-5/8” DECREASER
6” (152mm)
MINIMUM: 4ft. (1.22m)
MAXIMUM: 40ft. (12.19m)
TERMINATION CAP
TERMINATION CAP
Slide restrictor into exhaust pipe on top of fireplace with tabs
pointing towards you prior to attaching venting.
Figure 19b
Figure 19a
NOTE
Page 29 has information on restrictor recommendations depending on burner flame appearance and instructions on installation
after venting is completed.
CAUTION This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.
NOTE
Horizontal Vent Heat Shield is not used on vertical venting configurations.
Depending on your particular venting needs, a Decreaser may be necessary to terminate venting system.
Large Restrictor Remove tab (s) to
create small restrictor
Bend tabs to approx. 80 degree
angles to create tension to hold
itself in place when installed.
Figure 19c
NOTE