System Timer Descriptions
Partial Arm Entry Time
The Partial Arm Entry time is the delay time that will be allocated to all active zones in Partial Arm Mode. Fire and 24 Hour
Zones will not be affected in Partial Arm Mode. The valid time selection in this segment is 10 to 255 seconds.
Strobe Time
The strobe time is the duration that output programmed to follow the strobe time will activate. The valid time selection in this
segment is 0 to 255 hours, where ‘0’ = Latching.
Dynamic Battery Test
The panel can perform a Dynamic Battery Test for the duration in this segment at the disarming of the first area after
00:00 hours once each 24-hour cycle. This option is enabled by programming a test duration in this segment. The valid time
selection in this segment is 1 to 255 minutes.
AC Fail Report
The number programmed in this segment represents the number of 1 minute increments the AC power is lost before a
communication is initiated, from 1 to 255 minutes. The AC power restore will also delay reporting until after the number of
minutes programmed in this feature has elapsed.
Siren Time
The Siren Time is the duration that the siren output and auxiliary outputs programmed to follow the siren time will activate.
The valid time selection in this segment is 1 to 255 minutes.
Twin Trip Time
This segment contains the number of one (1) minute increments in the Twin Trip Zone Time Period. The Twin Trip Zone
Time Period can be programmed in one (1) minute increments from 1 to 255. The time programmed in this feature will set
the time period whereby two or more zones must trip before an alarm condition will be registered or the one zone must
trigger twice within this time period, or a continuous trip longer than 10 seconds.
Chime Option
The code pad chime is a true chime sound, which can be set to follow the input status, chime once, or latch until a valid
code is entered. The options programmable in this segment are: ‘0’ = Follow, ‘5’ = Chime once or ‘255’ = Latch.
Dialer Delay Time
The panel can delay the dialling of all non 24-hour zones by the duration programmed in this feature. The valid time
selection in this segment is 0 to 255 seconds.
Fire Alarm Verification Time
When enabled, the panel will verify a fire alarm by requiring more than one trip on a smoke detector within the time
programmed in this segment before creating an alarm. The valid time selection in this segment is 120 to 255 seconds.
Zone Inactivity Time
This option is used to set the Zone Inactivity Time in days from 1 to 255. This option is used in conjunction with the Zone
Activity Monitor that is set in the Characteristics of the Zone Configuration Group Type.
If Feature 22 – Segment 6 – Option 3 is enabled then this time is in hours not in days, from 2 to 255 hours.
Auxiliary Output 1 – 4 Configuration
Feature 26 Auxiliary Output 1-4 Area Selection
Feature 26 is used to select which area(s) the events must occur in before the output will activate. Feature 26 has 4
segments. Segment 1 corresponds to output 1, and Segment 4 corresponds to output 4.
Area 1 Area 2 Area 3 Area 4 Area 5 Area 6 Area 7 Area 8
Segment 1 – Output 1 (1) (2) (3) (4) (5) (6) (7) (8)
Segment 2 – Output 2 (1) (2) (3) (4) (5) (6) (7) (8)
Segment 3 – Output 3 (1) (2) (3) (4) (5) (6) (7) (8)
Segment 4 – Output 4 (1) (2) (3) (4) (5) (6) (7) (8)