Feature 23 Siren / Communicator Attempt Counter
Segment 1 0
Feature 23 is used to set the burglary zone siren / communicator attempt counter. The number programmed in segment 1
will determine the number of alarm activations the Hills Reliance will allow before bypassing all burglary zones (1-128) that
have tripped during the arming cycle. The bypassed zones will not report trips to a base station, and the local siren or bell
will not sound for these zones. A zone trip will not be added to the number count until the zone has tripped more than once.
For this option to be valid, sirens and or the communicator must be set to unlimited in system options.
Feature 24 Code Pad Sounder Control
The panel can set the code pad sounder for most alarm conditions. Feature 24 provides 8 system alarms that can be
enabled to set the code pad sounder. A code pad sounder activation can be silenced by entering a valid user code. Note.
The AC power fail and low battery code pad sounder activations will occur the instant these conditions are present. All
options in this feature are global to all code pads.
Segment 1
(1)
On if code pad sounds for ‘Telephone Line Cut‘ when the system is armed
(2)
On if code pad sounds for ‘Telephone Line Cut‘ when disarmed
3
On if code pad sounds upon AC Power Failure
4
On if code pad sounds when a Low Battery is detected
5
On if code pad sounds during Twin Trip time
(6)
On if code pad sounds for Zone and Box Tampers
7
On if code pad sounds for Medical Alarm
8
On if code pad sounds for Expander Trouble
System Timer Configuration
Feature 25 new System Timers
Feature 25 contains the duration of various system timing functions. Example: If you desire the duration of the Strobe time
to be 48 hours, you should program [4]-[8]-[] in segment 2 of this feature. The [4]-[8] is the number of hours, and the []
stores the data and moves to the next segment of this feature.
Seg 1 Seg 2 Seg 3 Seg 4 Seg 5 Seg 6 Seg 7 Seg 8 Seg 9 Seg 10 Seg 11 Seg 12 Seg 13 Seg 14
Segments 1-14 20 0 2 30 5 5 5 0 120 0 0 0 0 0
Segment 1
Partial Arm Entry Time (10 – 255 sec)
Segment 2
Strobe Time (0 – 255 hours)
Segment 3
Dynamic Battery Test Duration (0 – 255 min)
Segment 4
AC Failure Report Delay (0 – 255 min)
Segment 5
Siren Time (1 – 255 min)
Segment 6
Twin Trip Time (0 – 255 min)
Segment 7 new
Chime Option (‘0’ = Follow, ‘5’ = Chime once, ‘255’ = Latch)
Segment 8
Dialer Delay Time (0 – 255 sec)
Segment 9
Fire Alarm Verification Time (120 – 255 sec)
Segment 10 new
Reserved
Segment 11 new
Zone Inactivity Time (default is in days, see Feature 22 – Segment 6 – Option 3)
Segment 12 new
Reserved
Segment 13 new
Reserved
Segment 14 new
Reserved