Installation manual
24
FEATURE 23 SIREN / COMMUNICATOR ATTEMPT COUNTER
SEGMENT 1
0
Feature 23 is used to set the burglary zone siren / communicator attempt counter. The number programmed in
segment 1 will determine the number of alarm activations the NX-16 will allow before bypassing all burglary zones
(1-48) which have tripped during the arming cycle. The bypassed zones will not report trips to a base station, and
the local siren or bell will not sound for these zones. A zone trip will not be added to the number count until the
zone has tripped more than once. For this option to be valid, sirens and or the communicator must be set to
unlimited in system options.
FEATURE 24 CODE PAD SOUNDER CONTROL
The NX-16 can set the code pad sounder for most alarm conditions. Feature 24 provides 8 system alarms that can
be enabled to set the code pad sounder. A code pad sounder activation can be silenced by entering a valid user
code. Note. The A.C power fail and low battery code pad sounder activations will occur the instant these condition
are present. All options in this feature are global to all code pads.
SEGMENT 1
(1)
On if code pad sounds for Telephone Line Cut when the system is armed
(2)
On if code pad sounds for Telephone Line Cut when disarmed
3
On if code pad sounds upon AC Power Failure
4
On if code pad sounds when a Low Battery is detected
5
On if code pad sounds during Twin Trip time
(6)
On if code pad sounds for Zone and Box Tampers
7
On if code pad sounds for Medical Alarm
8
On if code pad sounds for Expander Trouble
SYSTEM OPTIONS TABLE
50 Hz Ac Synchronization
The NX-16 synchronizes its internal clock to the 50 HZ it receives from the AC input. If enabled, the NX-16 can generate its
own internal clock synchronization if you are installing the NX-16 where there is no AC power and battery is used.
Auto Partial Arm Area One
If enabled, area one will auto partial arm at the auto arm time. If this option is enabled, area one cannot be auto armed in the
full mode.
Battery Testing
The NX-16 will test the battery at disarm once per 24 hour cycle, if programmed in system timers. The NX-16 can test for
battery presence every 12 seconds. The battery missing test is enabled in this section.
Box Tamper
If enabled, the NX-16 will use the N/C Box Tamper pins provided on the main board.
Dual End Of Line (Zone Tamper)
If enabled, the NX-16 will monitor all zones except types 17 and 28 for Dual End Of Line. A short or open circuit on a DEOL will
set zone tamper alarms. Refer to the terminal wiring diagram for more detail.
Expanded Contact I.D.
The NX-16 can report all system device alarms with their individual point number if the expanded contact I.D. reporting is
enabled.