Installation manual

18
FEATURE 16 AREA 1 - OPTIONS
Feature 16 is used to enable certain options that can be accessed or are visible to the user from the code pad of
the system. In addition, certain communicator reports are enabled in Feature 16. Each of these options can be
enabled by area. For additional area information see Features 37-58 on pages 19-21. If the option selection
feature for any area is left blank, that area will use this feature for the option selection. This feature contains
3 segments of 8 options each.
SEGMENT 1
(1) On enables the Quick Arm option
(2) On enables the Re-exit option
3 On enables the Force Arm option
4 On enables the Silent Code Pad Panic option
(5) On enables the Audible Code Pad Panic option
(6) On enables the Code Pad Fire option
(7) On enables the Code Pad Medical option
8 On enables the Code Pad Multiple Code Attempt Tamper option
SEGMENT 2
1 On enables the LED Extinguish option.
2 On enables the Require Code for Bypassing option
3 On enables the Zone Bypassed Sounder Alert option
(4) On enables the AC Power/Low Battery Sounder Alert option
(5) On enables Bypass toggle
6 On enables Silent Auto Arm
7 On enables the Universal Arming option
8 On enables the One Key Partial Mode Disarm
SEGMENT 3
(1) On enables Opening and Closing reports
(2) On enables Zone Bypass reporting
(3) On enables Zone Restore reporting
(4) On enables Zone Trouble reporting
(5) On enables Zone Tamper reporting
6 On enables the Cancel option
(7) On enables Recent Closing option
(8) On enables Exit Error option
FEATURE 17 AREA 1 - ENTRY / EXIT TIMERS
SEGMENTS 1-4
ENTRY TIME 1 - 30 EXIT TIME 1 - 60 ENTRY TIME 2 - 30 EXIT TIME 2 - 60
Feature 17 sets the primary and secondary entry / exit times for area 1. Valid entries are 10-255 seconds
AREA OPTIONS TABLE
AC Power / Low Battery Sounder Alert
If enabled, the NX-16 will beep the Code Pad sounder upon arming or disarming if the AC power is missing or a low battery
has been detected.
Bypass Code
If enabled, the NX-16 will require a valid user code to be entered during the zone bypass function.
Cancel
If enabled, the NX-16 will send a "Cancel" report when the system is disarmed by a valid user after an alarm activation. The
cancel code followed by the user number.
Code Pad Activated Panics
The NX-16 has three Code Pad activated panics that will send reports to the central station: Fire, Medical, and Code Pad
Panic. The Fire key will activate the steady (Fire) siren, the Medical key will sound the Code Pad ( the Medical key can be set
for silent activation in system options), and the Code Pad Panic can be programmed to be silent or audible (sound siren