TERMINAL DESCRIPTION TABLE
TERMINAL DESCRIPTION
EARTH
Earth Ground. Connect to a cold water pipe or a 1 to 3 metre driven rod.
AC
AC input. Connect to a 16.5V 25, 40 or 50 VA approved transformer.
BELL + &
BELL -
If used as a siren output(default), the speaker rating should be 15 watt at 8 or 16 ohm, or 30/40
watt at 4, 8, or 16 ohms. If voltage output is selected in Feature 37, this output becomes voltage
output, 12VDC, 1 Amp maximum load. NOTE: A 3.3K resistor may be required across the
bell terminals when a 12 VDC siren is used . If no resistor is used, you may experience
voltage leakage into the siren which will cause these devices to output a small signal.
KP DATA
Connect to the data terminal on the code pads and the expanders. Maximum total wire run is 800
metres using 14/020 cable. These numbers are for one code pad at the end of the wire. When
connecting more than one code pad to the end of the wire, a higher gauge wire or a reduction in
total wire distance will be required.
KP COM
Connect to the Common terminal on the code pads and the expanders.
KP POS
Connect to the Positive terminal on the code pads and the expanders. This terminal and AUX
PWR + are limited to 1 amp total current when added together.
SMOKE+
Smoke detector power 12VDC, 500 ma maximum.
COM
Connect negative wire of powered devices such as motion detectors and smoke detectors.
AUX PWR+
Connect positive wire of all powered devices accept smoke detectors and code pads. This terminal
and KP POS are limited to 1 amp total current when added together.
ZONE 8
Connect to one side of zone 8 loop. Connect the other side to com terminal. Open or short causes
alarm. Zone 8 may be used for a two wire smoke detector using a 680W E.O.L. resistor. W3
must be set for two wire smoke detector loop. For normal zone operation, W2 must be set.
COM
Common (-) terminal for zones 7 & 8. (See the wiring diagram for examples.)
ZONE 7
Connect to one side of zone 7 loop. Connect the other side to COM terminal. Open or short causes
alarm.
ZONE 6 -
ZONE 1
Connect as described for zones 7 & 8. Only zone 8 can be a two wire zone. (See the wiring
diagram for examples.)
AUX
RELAY
OUT 1-2
Relays one and two switch a 12 volts output on their N/C and N/O terminals. This means that you
connect the positive lead of you device to these terminals, and connect the negative lead to the
“Com” terminals.