Service manual
Electrical schematics
This illustration shows the complete controller connections, internal as well as external:
1=Gnd
2=B
3=Gnd
4=A
5-6=12v line pwr
7-8=line pwr gnd
TTL
SD
J2
J7
J4
J1
RS 485
J15
J5
J11
J16
J22
3: Supply GND
2: NC
1: Supply 12V
8: Evap out sens GND
7: Evap out sens signal
6: Evap in sens GND
5: Evap in sens signal
4: Cond sens GND
3: Cond sens signal
2: Ret. Sens GND
1: Ret. Sens signal
4: Voltage sensor
3: Voltage sensor
2: Current sensor
1: Current sensor
6: +12V
5: +12V
4: \B
3: \A
2: B
1: A
Valve
Relay drive out
0/12V DC 200mA
Fan 1
Fan 2
Fan 3
External
interfaces
Alarm
AC 1
Power sensors
Temp sensors
NTC -30 to 85°C
(-22 to 185°F)
Supply
6: Cond fan relay out.
5: Cond fan relay 12V
4: Heater relay out.
3: Heater relay 12V
2: Compressor relay out
1: Compressor relay 12V
4: GND
3: Tacho
2: PWM
1: NC
4: GND
3: Tacho
2: PWM
1: NC
3: GND
2: Tacho
1: PWM
9: Hotspot sens GND
8: Hotspot sens.
7: Dig GND
6: Dig2 input
5: Dig1 input
4: AC1 relay contact
3: AC1 relay contact
2: Alarm 1 relay contact
1: Alarm 1 relay contact
Standard shielded ethernet
cable (568A termination)
Accessory
TTL interface
(galvanic isolated)
NTC -30 to 85°C
(-22 to 185°F)
Active low
max 12V DC/10mA
Max. 42 VAC or 60 VDC. /
500mA. Default normally
open - jumper changeable
Max. 42 VAC or 60 VDC. /
500mA. Default normally
open - jumper changeable
Fig. 14
Overall controller
Technical data
These units are designed for high reliability and electrical eciency.
• Compressor is a rotary type with high eciency.
• Radial fans with backward curved impellers.
• Slim MPE Condenser for high performance thus low pressure drop.
This table shows the technical data for 4000 BTU models.
Specication Unit 115 VAC units 230 VAC units
Unit dimensions
(height×width×depth)
Inch. 29 x 17.3 x 11.3
Weight
lbs. 70
Operational temperature range
°F -40-+131
Storage temperature / humidity
°F /RH% -40-+176 / 0-99
Noise level, outside 2m distance at
80.6°F. internal / 95°F. Ambient
dB(A) 65
IP protection EN 60529
IP class 65
Outdoor Enclosure acc. UL 50
Type 3R
Refrigerant type / amount
Type/lbs R134a /210g
Cooling capacity at 80.6°F
internal/95°F Ambient (total)
BTU/h 4092
EER Air conditioning at 95°F internal /
95°F Ambient
BTU/h 5.2
Internal airow
CFM 679
External airow
CFM 798
Input voltage range
VAC 115 +/-10% 230 +/-10%
Frequency
Hz 60 50/60
Power consumption
Circulation / Air Conditioning
W 48/740
Power consumption Heater
W 1000 1000
LRA (locked rotor current)*
A 37* 17*
Extension cord dimension
awg 14 14
*Recommended over current protection specication to be found on page 5
Introduction
4000 btu. units
086161 • Version 1.0 • 15.07.2014
23
22
en