Operating instructions
 ecoCOOLING Combo Installation, Operating & Maintenance Manual 
Doc Ref:    Page 8 of 14 
EcoCooling IOM Manual RevA 
5  MAINTENANCE 
5.1  Trouble Shooting 
The air conditioners are designed for trouble free life as long as the ambient filter (if applicable) is maintained 
in a clean condition. To aid in service definition the service personnel can initially identify probable cause by 
referring to the following trouble shooting chart. 
If in doubt contact Dantherm Air Handling Inc. for assistance. Always have the Model #, Serial # 
available before you call. 
Problem 
Potential Cause 
Solution 
Unit not running 
No Power 
Check power source and electrical 
connections 
Fuse Blown on Control Board 
Replace with fuse 
Faulty control components 
Carry out self test 
Unit not cooling sufficiently  
Filter (if applicable) clogged 
Clean or replace filter 
Blocked evaporator or condenser 
coil 
Clean coil 
Evaporator or condenser blower 
not operating 
Replace motor, capacitor or entire 
assembly 
Loss of refrigerant or oil leaks 
Locate and repair leak. Replace charge 
Insufficient capacity 
Contact Dantherm Air Handling, Inc. 
Ice on evaporator coil 
Insufficient heat load or unit 
oversized for application 
Contact Dantherm Air Handling, Inc. 
Failed evaporator blower 
Replace evaporator blower motor or 
assembly 
Condensate draining 
continuously 
Enclosure not properly sealed 
Check and seal all openings 
Excessive vibration 
Loose compressor, fans or tubing 
Locate and correct 
Missing Compressor 
Current (F=01) 
Faulty compressor 
Replace compressor 
Broken current sensor 
Replace Control Board 
Wire detached or improperly 
installed 
Secure wiring or install wiring properly 
according to diagram 
High Pressure Alarm (F=02) 
Faulty condensor fan or wiring 
loose 
Replace fan or check wiring to fan 
Faulty condensor fan capacitor or 
wiring loose 
Replace capacitor or check wiring to 
capacitor 
Faulty condensor fan switch or 
high pressure switch 
Replace appropriate switch 
Low Pressure Alarm after 
start (F=03) 
Slow leak in system 
Locate and repair leak. Replace charge 
Low Pressure Alarm before 
start (F=04) 
No refrigerant in system (Large 
leak) 
Locate and repair leak. Replace charge 
Low charge in system 
Locate and repair leak. Replace charge 
High Temperature Alarm 
(F=05) 
Unit undersized for application 
Contact Dantherm Air Handling, Inc. 
Low Temperature Alarm 
(F=06) 
Insufficient heat load or unit 
oversized for application 
Contact Dantherm Air Handling, Inc. 
Faulty Temperature Sensor 
(F=07) 
Sensor not connected 
Reconnect sensor 
Faulty sensor 
Replace sensor 