7.4.4 RFI Filter
1. Remove the red/black cables from the filter cable.
2. Remove the protective foil.
3. Remove the 3 filter cables screws using a hex 8
key.
4. Remove the 2 screws (T20) from the EMC shield.
5. Remove the EMC shield.
6. Remove the 8 screws (T20) on the filter cable
cover.
7. Loosen the left cable connector using a hex 5 key
8. Remove the entire filter assembly.
Reinstall in the reverse order.
130BC126.11
1
2
3
Illustration 7.10 RFI Filter
1 RFI filter
2 Screws
3 EMC shield
Table 7.10
7.4.5
Relay Transducer Card
1. Unplug cables on the relay transducer card.
2. Loosen the right cable connector using a hex 5
key.
3. Open the plastic clamp to remove the cables
from the connector.
4. Remove the 2 screws (T20) from the holding
bracket.
5. Remove the holding bracket.
6. Remove the 3 cable screws (T20).
7. Remove the 3 screws on relay card (T20).
8. Remove the Relay card by pushing in the
retaining clips on the standoffs. Use a screwdriver
if necessary.
9. Remove the mounting plate.
Reinstall in the reverse order.
1
2
130BC127.11
Illustration 7.11 Relay or Transducer Card
1 Relay transducer card
2 Relay card mounting plate
Table 7.11
H-Frame Size Disassembly a...
VLT
®
HVAC Basic Drive Service Manual
MG90X202 - VLT
®
is a registered Danfoss trademark 63