Service manual
7.3.5 RFI Filter
1. Remove the protection cover.
2. Remove the 6 distance bushes.
3. Remove the 2 screws on the frame side.
4. Remove the 3 screws from U V W cables.
5. Press the barbs on the side of the filter.
6. Remove the RFI filter.
Reinstall in the reverse order.
130BC111.11
1
2
Illustration 7.5 RFI Filter
1
RFI filter
2 EMC shield
Table 7.5
7.3.6
Power Card
1. Remove the 3 screws on the U V W cable
connector.
2. Remove the connector.
3. Remove the 3 small screws (T10) from the power
card.
NOTE
If it is difficult to get out the screws, use a magnet.
4. Remove the 6 remaining screws (T20).
5. Lift the power card and slide it out of the frame.
Reinstall in the reverse order.
NOTE
If it is difficult to remove the power card, it is helpful to
press the frame sides outwards while pressing the barbs
on the side of the power card.
130BC112.11
1
2
Illustration 7.6 Power Card
1 Power card
2 Power card mounting plate
Table 7.6