Service manual

H10
Remove the front terminal cover to access the connectors.
The UDC terminals are located inside the frequency
converter.
130BC351.10
DC-
DC+
L1
L2
L3
V
W
U
Illustration 6.11 UDC Terminals Location on H10 Frequency
Converter
I7 and I8
Remove the IP54 front cover to access the +/- UDC
terminals, either on the power card MK900 or on MK3 on
the current sensor board.
130BC356.10
Illustration 6.12 +/- UDC Terminals on Power Card
130BC358.10
Illustration 6.13 +/- UDC Terminals on Current Sensor Board
130BC359.10
Illustration 6.14 +/- UDC Terminals on Current Sensor Board -
Close-up View
6.4 Dynamic Test Procedures
NOTE
Test procedures in this section are numbered for reference
only. Tests do not need to be performed in this order.
Perform tests only as necessary.
WARNING
Never disconnect the input cabling to the frequency
converter with power applied due to danger of severe
injury or death.
CAUTION
Take all the necessary safety precautions for system start-
up before applying power to the frequency converter.
Dynamic tests are conducted with the power applied to
the medium power size frequency converter.
Test Procedures
VLT
®
HVAC Basic Drive Service Manual
52 MG90X202 - VLT
®
is a registered Danfoss trademark
6