Instruction manual

Cascade Controller Option
system. Ensure that the staging frequency setting
allows the check valve to remain open.
Quick Menu 028 Par. 741 Destaging frequency
(STD DESTAGE FRQ)
Value:
0 - 100 % F
max
10%
Function:
The lead pump (pump 1 in the figure) typically
runs at minimum speed when destaging occurs.
Turning off a fixed speed pump (pump X in the
figure) creates a momentary pressure drop until the
lead pump decelerates. To avoid this, the drive
will accelerate to a Destaging frequency before
turning off the fixed speed pump.
Description of choice:
Adjust the Destaging frequency to the best
compromise to prevent momentary pressure drop
and over-pressurization during transition. A very low
value for the destaging frequency might cause the
check valve at the discharge of the lead pump to
close during the transition, which could add pressure
in the system. Ensure that the Destaging frequency
setting allows the check valve to remain open.
NOTE
Ensure that the Destaging frequency is
set within the Minimum and Maximum
frequency in par. 201 and 202.
MG.60.I5.22 - VLT is a registered Danfoss trademark