Instruction manual
Cascade Controller Option
■ Initial Setup
Instructions for programming Quick Menu items
1-20 are presented in Chapter 5, AFD and
Cascade Controller Card Setup . Parameters
1-20 must be programmed before programming
additional options described below.
Quick Menu 021 Par. 712 Motor Pump
Combinations
(PUMP COMBINATION)
Value:
(See options in table below)
Function:
The combinations of pumps and their rated capacities
are selected in this parameter. The lead pump (or
fan) with the cascade contol option must have a
capacity of 100% and its speed is controlled by the
AFD. This enables the highest accuracy in regulation
of the system. In Standard cascade control mode,
additional pumps can be either 100%, 200% or
300% relative to the AFD driven pump.
Description of choice:
Select the pump combination and capacities
from the choices offered.
Motor Pump Combinations
Value:
Additional Constant Speed Pumps Operated by Cascade Control
Display Option 100% Capacity 200% Capacity 300% Capacity
R6 @100%
1pumpcontrolledby
relay 6
R6, R7 @100% 2 pumps controlled by
relays 6, 7
R6-R8 @100% 3 pumps controlled by
relays 6, 7, 8
R6-R9 @100% 4 pumps controlled by
relays 6, 7, 8, 9
R6 @100%, R7 @200% 1pumpcontrolledby
relay 6
1pumpcontrolledby
relay 7
R6 @100%, R7, R8
@200%
1pumpcontrolledby
relay 6
2 pumps controlled by
relays 7, 8
R6, R7 @100%, R8
@300%
2 pumps controlled by
relays 6, 7
1 pump controlled by
relay 8
R6, R7 @100%, R8, R9
@300%
2 pumps controlled by
relays 6, 7
2 pumps controlled by
relays 8, 9
MG.60.I5.22 - VLT is a registered Danfoss trademark