Instruction manual
Cascade Controller Option
Extended Menu Par. 004 LCP Copy
(LCP COPY)
Value:
✭No copying (NO COPY)
[0]
Upload all parameters
(UPLOAD ALL PARAMET.)
[1]
Download all parameters
(DOWNLOAD ALL PARAM.)
[2]
Download power-independent parameters
(DOWNLOAD SIZE INDEP.)
[3]
Function:
This parameter is used to copy all parameter setups to
or from the Local Control Panel (LCP) keypad. It can
be used to store a backup copy of all parameters in the
LCP or to copy all setups from one drive to another.
Description of choice:
Select Upload all parameters to copy all parameter
values from the drive to the LCP.
Select Download all parameters to copy all
parameter values from the LCP to the drive on
which the keypad is mounted.
Select Download power-independent parameters if
only the power-independent parameters are to be
downloaded. This allows the parameters from one drive
to be easily copied to another drive of a different size.
Settings in parameters 102, 103, 104, 105, 106, 215,
221, and 222 are not downloaded using this function.
NOTE
Copying is only possible when drive is stopped.
MG.60.I5.22 - VLT is a registered Danfoss trademark
38