Cascade Controller Option
Description of choice:
Select a value that equals the nameplate data on the
motor, regardless of the AC input voltage of the AFD.
Quick Menu 004 Par. 104 Motor frequency
(MOTOR FREQUENCY)
Value:
50 Hz
✭ 60
60 Hz
Function:
This is where the rated motor frequency is selected.
Description of choice:
Select a value that equals the nameplate
data on the motor.
Quick Menu 005 Par. 105 Motor current
(MOTOR CURRENT)
Value:
0.01 - Drive rating
✭ Depends on motor
Function:
The rated motor current in amps forms part of the AFD
calculations for torque and motor thermal protection.
Description of choice:
Set a value that equals the nameplate data on the motor.
NOTE
It is important to enter the correct value, since
this forms part of the VVC
+
control feature.
Quick Menu 006 Par. 106 Rated motor speed
(MOTOR NO M. SPEED)
Value:
100 - 60000 rpm
✭ Depends on parameter 102, Motor power
Function:
This is where the value is set that corresponds to the
rated motor speed found on the nameplate data.
Description of choice:
Set a value that corresponds to the motor
nameplate data.
NOTE
It is important to set the correct value, since
this forms part of the VVC
+
control feature.
The maximum value equals frequency x 60. Frequency
is set in parameter 104, Motor frequency.
Quick Menu 007 Par. 201 Output frequency
low limit
(MIN. FREQUENCY)
Value:
0.0 - Parameter 202 setting
✭ 0.0 HZ
Function:
This is where to select the minimum output frequency.
The drive will be unable to run continuously
below this value in any mode.
Description of choice:
Set a value from 0.0 Hz to the Output frequency high
limit set in Quick Menu item 008 (parameter 202).
Quick Menu 008 Par. 202 Output frequency
high limit
(MAX. FREQUENCY)
Value:
Para 201 setting - Para 200 limit
✭ 60 Hz
Function:
In this parameter, a maximum output frequency can be
selected that corresponds with the maximum motor
speed. The drive will not be able to run continuously at
an output frequency above this value in any mode.
NOTE
Set the output frequency high limit to
60 Hz for US applications. The output
frequency of the AFD can never assume a
value higher than 1/10 of the switching frequency
(parameter 407, Switching frequency).
Description of choice:
Enter a value between the low frequency limit, set
in Quick Menu item 07 (parameter 201), and the
frequency range limit, set in parameter 200.
MG.60.I5.22 - VLT is a registered Danfoss trademark
32