Instruction manual
Cascade Controller Option
■ Language
Quick Menu 001 Par. 001 Languag e
(LANGUAGE)
Value:
✭English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
Swedish (SVENSKA)
Dutch (NEDERLANDS)
Portuguese (PORTUGUESA)
Finnish (SUOMI)
Function:
This choice defines the language to be used
on the display.
Description of choice:
Select the display language.
NOTE
It is important that the values set in parameters
102-106, Motor nameplate data, correspond
to the nameplate data of the motor.
■ Motor nameplate data
Quick Menu 002 Par. 102 Motor power
(MOTOR POWER)
Value:
0.1/3 HP (0.25 KW)
[000.25]
0.5 HP (0.37 KW)
[000.37]
0.75 HP (0.55 KW)
[000.55]
1.0 HP (0.75 KW)
[000.75]
1.5 HP (1.10 KW)
[001.10]
2 HP (1.50 KW)
[001.50]
3 HP (2.20 KW)
[002.20]
4 HP (3.00 KW)
[003.00]
5 HP (4.00 KW)
[004.00]
7.5 HP (5.50 KW)
[005.50]
10 HP (7.50 KW)
[007.50]
15 HP (11.00 KW)
[011.00]
20 HP (15.00 KW)
[015.00]
25 HP (18.50 KW)
[018.50]
30 HP (22.00 KW)
[022.00]
40 HP (30.00 KW)
[030.00]
50 HP (37.00 KW)
[037.00]
60 HP (45.00 KW)
[045.00]
75 HP (55.00 KW)
[055.00]
100 HP (75.00 KW)
[075.00]
125 HP (90.00 KW)
[090.00]
150 HP (110.00 KW)
[110.00]
200 HP (132.00 KW)
[132.00]
250 HP (160.00 KW)
[160.00]
300 HP (200.00 KW)
[200.00]
350 HP (250.00 KW)
[250.00]
400 HP (300.00 KW)
[300.00]
450 HP (315.00 KW)
[315.00]
500 HP (355.00 KW)
[355.00]
600 HP (400.00 KW)
[400.00]
✭Depends on the unit
Function:
This sets the power value that corresponds to the
nameplate power of the motor. The default setting
is the full rating of the drive. The drive can operate
motors undersized by up to four ratings below the full
rating of the drive or oversized by one rating.
Description of choice:
Select a value that equals the nameplate data
on the motor. tage
Quick Menu 003 Par. 103 Motor voltage
(MOTOR VOLTAGE)
Value:
200 V
[200]
208 V
[208]
220 V
[220]
230 V
[230]
240 V
[240]
380 V
[380]
400 V
[400]
415 V
[400]
440 V
[440]
460 V
[460]
480 V
[480]
500 V
[500]
✭Depends on motor
Function:
This is where the rated motor voltage is selected.
MG.60.I5.22 - VLT is a registered Danfoss trademark
31
AFD and Cascade
Controller Setup