Instruction manual

Cascade Controller Option
Quick Menu Summary
Quick Menu
number
Parame-
ter num-
ber
Name Units Range Factory setting
Basic Drive Set Up parameters
001 001 Language 10 languages See Instruction Manual for your
AFD model.
002 102 Motor Power kW/HP 1.1-450/1.5-600
003 103 Motor Voltage Volts 200 - 480
004 104 Motor Frequency Hz 50 / 60
005 105 Motor Current Amps 0- AFD max
006 106 Rated Motor Speed RPM 0- fm,n x 60
007 201 Min. Frequency Hz 0.0 - fmax 2/5 of fnom (NEW)
008 202 Max. Frequency Hz Fmin-120/1000 Fnom x 1.1 (NEW)
009 206 Ramp up time Seconds 1-3600 Seetableabovein2.4.8
010 207 Ramp down time Seconds 1-3600
011 323 Relay 1 Output Depending on choice See AFD Instruction Manual.
012 326 Relay 2 Output
Basic Set Up for Standard Cascade and Master/Slave.
013 415 Closed loop units Selected according to your process.
014 413 Minimum Feedback
015 414 Maximum Feedback
016 227 Warning low Feedback Units -999,999.999- FB High -999,999.999
017 228 Warning high Feedback Units FB low- 999,999.999 999,999.999
018 204 Ref.min. Units Min. feedback - Ref.max 0
019 205 Ref.max. Units Ref.min - Max. feedback 0
020 723 Operational Mode select - Standard / M/S Standard Cascade
021 712 Pump combination 1-8 1
022 713 Staging BandW. % 1.0 - 100.0 10.0
023 714 Destaging Delay Sec. 0.0 - 3000 15
024 715 Staging Delay Sec. 0.0 - 3000 15
025 716 Override BW %ofsetpoint 2.0 - 100.0 20.0
026 717 Override Timer Sec. 0.0 - 300 5
027 718 Staging frequency %offmax 0-100 90
028 741 Destaging frequency %offmax 0-100 10
029 418 Setpoint 1 (H0) Bar (or equiv.) Refmin - Refmax 0.000
030 419 Setpoint 2 (H1) Bar (or equiv.) Refmin - Refmax 0.000
031 721 Destage Timer Timer Sec. 0.0 - 300 (301 = OFF) 15
032 722 Pump cycling Enabled/Disabled Enabled
033 319 Analog/digital outputs - [1] - [43] Fout020mA
034 739 M/S Stage on frequencies Hz Fmin-Fmax Fmin
035 740 M/S stage off frequencies Hz Fmin-Fmax Fmax
036 750 Alternation time Hrs 0-999 0
037 751 Elapsed alternation time Hrs 0 - par. 750 0
038 752 Alternation register 1-4 1
039 753 Alternation restart delay Sec. 0-60 5
PID Controller tuning
040 420 Normal/Inverse control Normal/Inverse Normal mode
041 422 PID Start up frequency Hz Fmin-fmax 0Hz
042 427 PID Lowpass filter time Sec. 0.01 - 10.00 1.00
043 423 PIDProportionalGain Factor 0.00 - 10.0 0.01
044 424 PID Integrator time Sec. 0.01 - 9999.0 OFF
MG.60.I5.22 - VLT is a registered Danfoss trademark