Instruction manual
Cascade Controller Option
■ Parameter setting procedure
Enter or change parameter data or settings as follows:
1. Press [Quick Menu] or [Extended Menu] key.
2. Use [+] and [-] keys to find parameter
you choose to edit.
3. Press [Change Data] key.
4. Use [+] and [-] keys to select correct parameter
setting. To move to a different digit within a numeric
parameter, use < and > arrows. Flashing cursor
indicates digit selected to change.
5. Press [Cancel] key to disregard change, or press
[OK] key to accept change and enter new setting.
■ Example of how to change parameter data
Assume Quick Menu item 9 (parameter 206, Ramp
Up Time) is set at 60 seconds. Change the ramp
up time to 100 seconds as follows:
1. Press [Quick Menu] key.
2. Press [+] key until you reach Quick Menu item 9
of 35 (parameter 206), Ramp Up Time.
3. Press < key twice – hundreds digit will flash.
4. Press [+] key once to change hundreds digit to ‘1.’
5. Press > key once to move to tens digit.
6. Press [-] key until ‘6’ counts down to ‘0’ and
setting for Ramp Up Time reads ‘100 s.’
7. Press [OK] key to enter new value.
■ Manual initialization
The drive can be initialized to return to factory
default settings.
NOTE
Initializing the drive will remove all values and
settings entered into drive. Some factory default
settings may be for European applications.
1. Remove AC power to drive.
2. Press and hold [DISPLAY MODE] + [CHANGE
DATA] + [OK] keys down while at same time
applying AC power to drive.
3. Release keys. AFD reverts to factory setting.
It is also possible to carry out initialization via parameter
620, Operating mode, by selecting Initialize.
The following parameters are not reset when
using manual initialization:
500, Protocol
600, Operating hours
601, Hours run
602, kWh counter
603, Number of power-ups
604, Number of overtemperatures
605, Number of overvoltages
724 - 737, Operating hours/counters
MG.60.I5.22 - VLT is a registered Danfoss trademark
28