Instruction manual
Cascade Controller Option
■ Changed Drive functions
■ Introduction
Installation of the Cascade Controller Option card
into the AFD overrides some existing drive functions.
Changes to the default parameter setting are shown
in the tables below. Data entered into the drive
parameters are used to program the drive and cascade
controller for system operation. The modified parameter
default settings make programming the cascade
controller easier. See Chapter 5, User Interface,for
instructions on programming drive parameters.
In addition, parameters that need to be programmed
for cascade control operation are assembled
sequentially in a new and expanded 44 item Quick
Menu. Programming is simplified by following the
Quick Menu items in sequence for either Standard
cascade control or Master/Slave cascade control.
The new Quick Menu is described in Chapter 6,
AFD and Cascade Controller Card Setup.
New options are also available to stop pumps or fans
controlled in cascade operation. A summary of AFD
changed functionality is presented in this chapter.
Changed Default Settings with the Cascade Controller Option Card
Parameter Description Previous default New default
100 Configuration Open loop Closed loop
201 Minimum output freq. 0.0 Hz 40% of nominal frequency
205 Maximum reference 50/60 Hz 100%
206 Ramp-up time Varies with unit See table below
207 Ramp-down time Varies with unit See table below
304 Terminal 27 (digital input) Safety interlock
1
/Coasting
stop inverse
Coasting stop, inverse
308 Terminal 53 (analog in V) Reference No operation
314 Terminal 60 (analog in A) Reference Feedback (4-20 mA)
318 Function after time out No function Stop (sequence stop)
417 Feedback Function Maximum Virtual Control Curve
427 PID lowpass filter time 0.01 sec. 0.20 sec.
AFD Type Ramp Up (parameter 206) Ramp Down(parameter 207)
8005/6002 8011/6011 1sec. 1sec.
8016/6016 8062/6062 3sec. 2sec.
8072/6072 8302/6272 5sec. 3sec.
8352/6352 8600/6550 8sec. 5sec.
1
VLT 8000: Factory setting for US
MG.60.I5.22 - VLT is a registered Danfoss trademark