Instruction manual

Cascade Controller Option
Installation and
Wiring Instructions
Installation and Wiring Instructions
Installing the Cascade Controller Option Card
This chapter provides instructions for installing
the cascade controller option card into an AFD.
In Standard cascade control mode, the option
card installs into the AFD controlling up to four
additional motors. In Master/Slave mode, the
option card installs in the Master drive controlling
up to four additional slave drives.
Relay output connections vary according to the mode
of operation and configuration of the system. Typical
wiring diagrams are also provided in this chapter.
Adhere to all safety guidelines provided in the VLT
6000 Operating Instructions MG.60.AX.YY and the VLT
8000 Operating Instructions MG.80.AX.YY respectively.
For instructions on drive operation, see the Operating
Instructions manual for your AFD series.
T
orque tightening requirements
Tighten all fittings described in this chapter to 7.1
in-lbs (0.8 Nm), unless specified otherwise.
O
ptional transmitter connections
Terminals 12 and 13 provide a 24 VDC, 200 mA
power supply. This supply can be used to power
remote transmitters without need for an external
power supply. See wiring instructions in Chapter
10, Feedback Transmitter Wiring.
DANGER
AFD contains dangerous voltages when
connected to line voltage. Touching th
e
electrical parts may be fatal - even after
the equipment has been disconnected from mains.
6002 - 6005, 200-240 V: wait at least 4 minutes
6006/8006 - 6062/8062, 200-240 V: wait at least 15 minutes
6002 - 6005, 380-460 V: wait at least 4 minutes
6006/8006 - 6072/8072, 380-460/480 V: wait at least 15 minutes
6102/8102 - 6352/8352, 380-460/480 V: wait at least 20 minutes
6402/8402 - 6602/8652, 380
-460/480 V:
wait at least 40 minutes
6002/8002 - 6006/8006, 525-600 V: wait at least 4 minutes
6008/8008 - 6027/8027, 525-600 V: wait at least 15 minutes
6032/8032 - 6072/8072, 525-60
0V:
wait at least 30 minutes
6102/8052 - 6402/8402, 525-600/690 V: wait at least 20 minutes
6502/8502 - 6652/8652, 525-600/690 V:: wait at least 40 minutes
WARNING
Only a competent electrician should
carry out electrical installation.
Improper installation of motor or AFD
can cause equipment failure, serious injur y
or death. Follow this manual and National
Electrical Code and local safety codes.
CAUTION
Electronic components of AFD are
sensitive to electrostatic discharge
(ESD). ESD can reduce performance
or destroy sensitive electronic components.
Follow proper ESD procedures during installation
or ser vicing to prevent damage.
MG.60.I5.22 - VLT is a registered Danfoss trademark
9