Operating instructions
VLT
®
5000 FLUX
Programming
■ Introduction
Parameter group 3xx selects the analogue and digital inputs and outputs to the desired function. Also scaling
of the inputs and outputs is performed in this group. Inputs: Max frequency on inputs terminal 16, 17, 18, 19,
27, 32, and 33 is 5 kHz. (24Vpp). Max frequency on inputs terminal 29 is 65 kHz (24Vpp).
Max frequency for the encoder inputs terminal 73 - 78 is 250 kHz (5Vpp). Outputs: Analogue outputs terminal
42 and 45 are scaleable current outputs. Max frequency on digital outputs terminal 26 and 46 is 50kHz.
PNU Parameter Factory setting Range Changes 4-Setup
Conver-
sion Data
# description during operation index type
300 T
Terminal 16, input
Reset Yes Yes 0 5
301 T
Terminal 17, input
Freeze reference Yes Yes 0 5
302 T
Terminal 18 Start, input
Start Yes Yes 0 5
303 T
Terminal 19, input
Reversing Yes Yes 0 5
304 T
Terminal 27, input
Coasting stop, inverse Yes Yes 0 5
305 T
Terminal 29, input
Jog Yes Yes 0 5
306 T
Terminal 32, input
Choice of setup, msb/speed up Yes Yes 0 5
307 T
Terminal 33, input
Choice of setup, lsb/speed down Yes Yes 0 5
308 T
Terminal 53, analogue input voltage
Reference Yes Yes 0 5
309 T
Terminal 53, min. scaling
0.0 V 0.0 - 10.0 V Yes Yes -1 5
310 T
Terminal 53, max. scaling
10.0 V 0.0 - 10.0 V Yes Yes -1 5
311 T
Terminal 54, analogue input voltage
No operation Yes Yes 0 5
312 T
Terminal 54, min. scaling
0.0 V 0.0 - 10.0 V Yes Yes -1 5
313 T
Terminal 54, max. scaling
10.0 V 0.0 - 10.0 V Yes Yes -1 5
314 T
Terminal 60, analogue input current
Reference Yes Yes 0 5
315 T
Terminal 60, min. scaling
0.0 mA 0.0 - 20.0 mA Yes Yes -4 5
316 T
Terminal 60, max. scaling
20.0 mA 0.0 - 20.0 mA Yes Yes -4 5
317 T
Time out
10 sec. 0 - 99 sec. Yes Yes 0 5
318 F
Function after time out
Off Yes Yes 0 5
319 T
Terminal 42, output
0-n
MAX
0-20 mA Yes Yes 0 5
321 T
Terminal 45, output
0-n
MAX
0-20 mA Yes Yes 0 5
323 R
Relay 01, output
No operation Yes Yes 0 5
324 R
Relay 01, ON delay
0.00 sec. 0.00 - 600.00 sec. Yes Yes -2 6
325 R
Relay 01, OFF delay
0.00 sec. 0.00 - 600.00 sec. Yes Yes -2 6
326 R
Relay 04, output
No operation Yes Yes 0 5
327 P
Pulse reference, max. frequency
100 - 65000 Hz 5000 Hz Yes Yes 0 6
329 E
Encoder feedback pulse/rev.
1024 pulses/rev. 500 - 10.000 pulses/rev. Yes Yes 0 6
341 T
Terminal 46, digital output
No operation Yes Yes 0 5
342 T
Terminal 46, output, pulse scaling
5000 Hz 1 - 50000 Hz Yes Yes 0 6
350 E
Encoder monitoring
OFF No No 0 5
351 E
Encoder direction
Normal No Yes 0 5
355 T
Terminal 26, digital output
No operation Yes Yes 0 5
356 T
Terminal 26, output, pulse scaling
5000 Hz 1 - 50000 Hz Yes Yes 0 6
357 T
Terminal 42, Output minimum scaling
0 % 000 - 100% Yes Yes 0 6
358 T
Terminal 42, Output maximum scaling
100% 000 - 500% Yes Yes 0 6
359 T
Terminal 45, Output minimum scaling
0 % 000 - 100% Yes Yes 0 6
360 T
Terminal 45, Output maximum scaling
100% 000 - 500% Yes Yes 0 6
361 M
Max Tracking Error
OFF 000 - 999 rpm Yes Yes 0 6
362 K
KTY Sensor Type
KTY1 KTY 1-3 No Yes 0 5
See also Operation and Display for further
information regarding Changes during operation,
4-Setup and Conversion index.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A7.02 - VLT is a registered Danfoss trademark
89