Operating instructions

VLT
®
5000 FLUX
Programming
References and limits
Introduction
The purpose of the parameter group 2xx is selecting and adjusting references, ramping times and setting
limits for warnings.
Actual reference Resulting reference for speed/torque
External reference Reference on Terminals 53, 54 or 60, and puls and bus references
Preset reference Reference value from the internal four presets.
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
200 O
Output speed range/direction
Only clockwise, 0-4500
rpm
No Yes 0 5
202 O
Output speed high limit
3000 rpm n
MIN
-par. 200 No Yes -1 6
203 R
Reference Range
Min - max Yes Yes 0 5
204 M
Minimum reference
0.000 -100,000.000-Ref
MAX
Yes Yes -3 4
205 M
Maximum reference
1500.000 Ref
MIN
-100,000.000 Yes Yes -3 4
206 R
Ramp type
Linear Yes Yes 0 5
207 R
Ramp-up time 1
Depends on unit 0.01 - 3600 Yes Yes -2 7
208 R
Ramp-down time 1
Depends on unit 0.01 - 3600 Yes Yes -2 7
209 R
Ramp-up time 2
Depends on unit 0.01 - 3600 Yes Yes -2 7
210 R
Ramp-down time 2
Depends on unit 0.01 - 3600 Yes Yes -2 7
211 J
Jog ramp time
Depends on unit 0.01 - 3600 Yes Yes -2 7
212 Q
Quick stop ramp-down time
Depends on unit 0.01 - 3600 Yes Yes -2 7
213 J
Jog speed
200 rpm 0.0 - par. 202 Yes Yes -1 6
214 R
Reference function
Sum Yes Yes 0 5
215 P
Preset reference 1
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
216 P
Preset reference 2
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
217 P
Preset reference 3
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
218 P
Preset reference 4
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
219 C
Catch up/slow down value
0.00 % 0.00 - 100 % Yes Yes -2 6
221 T
Torque limit for motor mode
160 % 0.0 % - xxx % Yes Yes -1 6
222 T
Torque limit for generating
operation
160 % 0.0 % - xxx % Yes Yes -1 6
223 W
Warning: Low current
0.0 A 0.0 - par. 224 Yes Yes -1 6
224 W
Warning: High current
I
VLT,MAX
Par. 223 - I
VLT,MAX
Yes Yes -1 6
225 W
Warning: Low speed
0 rpm 0 - par. 226 Yes Yes -1 6
226 W
Warning: High speed
100.000 rpm Par. 225 - par. 202 Yes Yes -1 6
234 M
Motor phase monitor
Enable Yes Yes 0 5
235 P
Phase loss monitor
Enable No No 0 5
236 L
Low Speed Current
100% 0 – Motor size depended Yes Yes 0 6
237 M
Model Shift Speed
20% of n
nom
10 Hz Yes No 0 6
240 A
Acceleration Jerk 1
33% 0-100% No No 0 U16
241 A
Acceleration Jerk 2
33% 0-100% No No 0 U16
242 D
Deceleration Jerk 1
33% 0-100% No No 0 U16
243 D
Deceleration Jerk 2
33% 0-100% No No 0 U16
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A7.02 - VLT is a registered Danfoss trademark