163 Functional Stop Delay
(FUNC. STOP DELAY)
Value:
0-10 sec.
0
Function:
When stopping, this delay postpones the change
to the selected stop-function, unless DC-brake is
enabled. During this delay, the shaft will be held
at zero speed with full holding torque.
Description of choice:
Ensuring that the mechanical brake has locked the
load before the motor is in coast mode.
See Mechanical brake control.
164 Mechanical Brake Release Delay
(BRAKE REL. D ELAY)
Value:
0.01-2.00 sec
0.50 sec
Function:
When Mechanical Brake Release is selected as
start-function in Parameter 121, this delay describes
thetimeittakesforthebraketoopen. Duringthis
delay, the motor will be held a 0 RPM.
165 Mechanical Brake Initial Torque
(BRAKE INI TORQUE)
Value:
+/- p221
20%
Function:
When Mechanical Brake Release is selected as a
start-function in Parameter 121, this torque-level
will be built up against the closed brake prior to
brake release. When using the drive in a crane,
lift or hoist application with a mechanical brake,
this torque should be set to a value equal to the
torque present, when the brake opens.
166 Mechanical Brake Initial Direction
(BRAKE INIT DIR)
Value:
[Clockwise]
[Ref. dir.]
[Clockwise]
Function:
When Mechanical Brake Release is selected as
a start-function in Parameter 121, this Parameter
determines the direction of the initial torque applied
against the closed brake. In a crane application the
load will always be in the same direction, but in other
applications it may make sense to apply the torque
in the same direction as the reference.
167 Proportional Gain Boost, during
Mechanical Brake Release
(BRAKE GAIN BOO ST)
Value:
0-400%
100%
Function:
When Mechanical Brake Release is selected as
start-function in Parameter 121, this Parameter
defines an extra gain on P-part (Par. 417) of speed
PI-controller during the Mechanical Release Delay (Par.
164). Boosting the proportional gain, will minimise
the small movement on the motorshaft when motor
takes over the load from the mechanical brake.
= factory setting. () = display text [] = value for use in communication via serial communication port