Operating instructions
VLT
®
5000 FLUX
Programming
■ Load and motor
■ Introduction
The parameter group 100 - 199 provides the adjustments and settings for load and motor connected to
the frequency converter.
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
100 C
Configuration
Speed control, closed loop No Yes 0 5
101 T
Torque characteristics
High - constant torque No Yes 0 5
102 M
Motor power
Depends on the unit 0.18-500 kW No Yes 1 6
103 M
Motor voltage
Depends on the unit 200 - 500 V No Yes 0 6
104 M
Motor frequency
50 Hz No Yes 0 6
105 M
Motor current
Depends on the unit 0.01-I
VLT,MAX
No Yes -2 7
106 R
Rated motor speed
Depends on the unit 100-60000 rpm No Yes 0 6
107 A
Automatic motor adaptation, AMA
Adaptation off No No 0 5
115 S
Slip Compensating
100% -400% - +400% Yes Yes 0 3
116 S
Slip compensation time constant
0.50 sec. 0.05-5.00 sec. Yes Yes -2 6
119 H
High starting torque
0.0 sec. 0.0 - 0.5 sec. Yes Yes -1 5
120 S
Start delay
0.0 sec. 0.0 - 10.0 sec. Yes Yes -1 5
121 S
Start function
Coasting in start delay time Yes Yes 0 5
122 F
Function at stop
Coasting Yes Yes 0 5
123 M
Min. speed for activating function
at stop
0 rpm 0 - 600 rpm Yes Yes -1 5
124 D
DC holding current
50 % 0 - 100 % Yes Yes 0 6
125 D
DC braking current
50 % 0 - 160 % Yes Yes 0 6
126 D
DC braking time
10.0 sec. 0.0 - 60.0 sec. Yes Yes -1 6
127 D
DC brake cut-in speed
Off 0.0-par. 202 Yes Yes -1 6
128 M
Motor thermal protection
No protection Yes Yes 0 5
129 E
External motor fan
No Yes Yes 0 5
130 S
Start speed
0.0 rpm 0.0 - 600 rpm Yes Yes -1 5
131 I
Initial current
0.0 Amp 0.0-par. 105 Yes Yes -1 6
150 S
Stator resistance
Depends on unit Ohm No Yes -4 7
151 R
Rotor resistance
Depends on unit Ohm No Yes -4 7
152 S
Stator leakage reactance
Depends on unit Ohm No Yes -3 7
153 R
Rotor leakage reactance
Depends on unit Ohm No Yes -3 7
154 M
Main reactance
Depends on unit Ohm No Yes -3 7
156 P
Pole number
4-pole motor 2-100 No Yes 0 5
158 I
Ironloss resistance
10000 1 - 10000 No Yes 0 6
161 M
Minimum Inertia
Depends on unit Kgm
2
No Yes -4 7
162 M
Maximum Inertia
Depends on unit Kgm
2
No Yes -4 7
163 F
Functional stop delay
0 0 – 5 sec Yes Yes -1 7
164 M
Mech. brake release delay
0.5 sec 0.01 - 2.00 sec Yes Yes -2 U16
165 M
Mech. brake initial torque
20% +/- P221 Yes Yes -1 S16
166 M
Mech. brake initial direction
[0] Clockwise [0] Clockwise
[1] Ref. dir.
Yes Yes 0 U8
167 P
Proportional gain boost, during
brake release
100% 0-400% Yes Yes 0 S16