Operating instructions

VLT
®
5000 FLUX
Control Panel
(LCP)
Initialisation to factory setting
The frequency converter can be initialised to
factory settings in two ways.
I
nitialisation by parameter 620
- Recommended initialisation
Select parameter 620
Press [CHANGE]
Select "Initialisation"
Press the [OK] key
Cut off the mains supply and wait until
the display turns off.
Reconnect the mains supply - the frequency
converter is now reset.
This parameter initialises all except:
500 Serial communication address
501 Baud rate for serial communication
601-605 Operating data
615-617 Fault logs
Manual initialisation
Disconnect from mains and wait until the
display turns off.
Press the following keys at
the same time:
[Display/status]
[Change data]
[OK]
Reconnecting the mains supply while
pressing the keys.
Release the keys
The frequency converter has now been
programmed for the factory setting.
This parameter initialises all except:
600-605 Operating data
NB!:
Settings for serial communication and
fault logs are reset.
MG.55.A7.02 - VLT is a registered Danfoss trademark