Operating instructions

VLT
®
5000 FLUX
Installation
Extra protection (RCD)
ELCB relays, multiple protective earthing or earthing
can be used as extra protection, provided that local
safety regulations are complied with.
In the case of an earth fault, a DC content may
develop in the faulty current.
If ELCB relays are used, local regulations must be
observed. Relays must be suitable for protection
of 3-phase equipment with a bridge rectifier and
for a brief discharge on power-up.
Earth leakage current
Earth leakage current is primarily caused by the
capacitance between motor phases and the motor
cable screen. When an RFI filter is used, this
contributes additional leakage current, as the filter
circuit is connected to earth through capacitors.
The size of the leakage current to the ground depends
on the following factors, in order of priority:
1. Length of motor cable
2. Motor cable with or without screen
3. Switching frequency
4. RFI filter used or not
5. Motor grounded on site or not
The leakage current is of importance to safety during
handling/operation of the frequency converter if (by
mistake) the frequency converter has not been earthed.
NB!:
Since the leakage current is >3.5 mA, reinforced
earthing must be established, which is required
if EN 50178 is to be complied with. For
3-phased frequency converters, only fault current
relays which are suitable for protection against DC
currents (Din VDE 0664) are to be used. RCD fault
current relays type B comply with these requirements
according to the norm IEC 755-2.
The following requirements must be complied with:
- Suitable for protecting equipment with a
direct current content (DC) in the fault
current (3-phase rectifier)
- Suitable for power-up with short pulse-shaped
charging current to earth
- Suitable for a high leakage current.
MG.55.A7.02 - VLT is a registered Danfoss trademark