Operating instructions

VLT
®
5000 FLUX
Appendix
Compact, Mains supply 3 x 380 - 500 V
According to international requirements V
VLT type 5352 5452 5502
Normal overload current (110 %):
Output current I
VLT,N
[A] (380-440 V) 600 658 745
I
VLT, MAX
(60 s) [A] (380-440 V) 660 724 820
I
VLT,N
[A] (441-500 V) 540 590 678
I
VLT, MAX
(60 s) [A] (441-500 V) 594 649 746
Output S
VLT,N
[kVA] (400 V) 416 456 516
S
VLT,N
[kVA] (460 V) 430 470 540
S
VLT,N
[kVA] (500 V) 468 511 587
Typical shaft output [kW] (400 V) 315 355 400
[HP] (460 V) 450 500 550/600
[kW] (500 V) 355 400 500
High overload torque (160 %):
Output current I
VLT,N
[A] (380-440 V) 480 600 658
I
VLT, MAX
(60 s) [A] (380-440 V) 720 900 987
I
VLT,N
[A] (441-500 V) 443 540 590
I
VLT, MAX
(60 s) [A] (441-500 V) 665 810 885
Output S
VLT,N
[kVA] (400 V) 333 416 456
S
VLT,N
[kVA] (460 V) 353 430 470
S
VLT,N
[kVA] (500 V) 384 468 511
Typical shaft output [kW] (400 V) 250 315 355
[HP] (460 V) 350 450 500
[kW] (500 V) 315 355 400
Max. cable cross-section
to motor and loadsharing
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. cable cross-section
to brake
[mm
2
]
4,6
[AWG]
2,4,6
2x185
2x350 mcm
Normal overload current (110 %):
Rated input current I
L,N
[A] (380-440 V) 590 647 733
I
L,N
[A] (441-500 V) 531 580 667
High overload torque (160 %):
Rated input current I
L,N
[A] (380-440 V) 472 590 647
I
L,N
[A] (441-500 V) 436 531 580
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. pre-fuses (mains)
[-]/UL
[A]
1
700/700 900/900 900/900
Efficiency
3
0,98
Power loss Normal overload [W] 7630 7701 8879
High overload [W] 6005 6960 7691
Weight IP 00 [kg] 221 234 236
Weight IP 21/Nema1 [kg] 263 270 272
Weight IP 54/Nema12 [kg] 263 270 272
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply
with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply, motor and loadsharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)
MG.55.A7.02 - VLT is a registered Danfoss trademark
155