Operating instructions
VLT
®
5000 FLUX
Appendix
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
200 O
Output speed range/direction
Only clockwise, 0-4500
rpm
No Yes 0 5
202 O
Output speed high limit
3000 rpm n
MIN
-par. 200 No Yes -1 6
203 R
Reference Range
Min - max Yes Yes 0 5
204 M
Minimum reference
0.000 -100,000.000-Ref
MAX
Yes Yes -3 4
205 M
Maximum reference
1500.000 Ref
MIN
-100,000.000 Yes Yes -3 4
206 R
Ramp type
Linear Yes Yes 0 5
207 R
Ramp-up time 1
Depends on unit 0.01 - 3600 Yes Yes -2 7
208 R
Ramp-down time 1
Depends on unit 0.01 - 3600 Yes Yes -2 7
209 R
Ramp-up time 2
Depends on unit 0.01 - 3600 Yes Yes -2 7
210 R
Ramp-down time 2
Depends on unit 0.01 - 3600 Yes Yes -2 7
211 J
Jog ramp time
Depends on unit 0.01 - 3600 Yes Yes -2 7
212 Q
Quick stop ramp-down time
Depends on unit 0.01 - 3600 Yes Yes -2 7
213 J
Jog speed
200 rpm 0.0 - par. 202 Yes Yes -1 6
214 R
Reference function
Sum Yes Yes 0 5
215 P
Preset reference 1
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
216 P
Preset reference 2
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
217 P
Preset reference 3
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
218 P
Preset reference 4
0.00 % - 100.00 - 100.00 % Yes Yes -2 3
219 C
Catch up/slow down value
0.00 % 0.00 - 100 % Yes Yes -2 6
221 T
Torque limit for motor mode
160 % 0.0 % - xxx % Yes Yes -1 6
222 T
Torque limit for generating
operation
160 % 0.0 % - xxx % Yes Yes -1 6
223 W
Warning: Low current
0.0 A 0.0 - par. 224 Yes Yes -1 6
224 W
Warning: High current
I
VLT,MAX
Par. 223 - I
VLT,MAX
Yes Yes -1 6
225 W
Warning: Low speed
0 rpm 0 - par. 226 Yes Yes -1 6
226 W
Warning: High speed
100.000 rpm Par. 225 - par. 202 Yes Yes -1 6
234 M
Motor phase monitor
Enable Yes Yes 0 5
235 P
Phase loss monitor
Enable No No 0 5
236 L
Low Speed Current
100% 0 – Motor size depended Yes Yes 0 6
237 M
Model Shift Speed
20% of n
nom
10 Hz Yes No 0 6
240 A
Acceleration Jerk 1
33% 0-100% No No 0 U16
241 A
Acceleration Jerk 2
33% 0-100% No No 0 U16
242 D
Deceleration Jerk 1
33% 0-100% No No 0 U16
243 D
Deceleration Jerk 2
33% 0-100% No No 0 U16
See also Operation and Display for further
information regarding Changes during operation,
4-Setup and Conversion index.
MG.55.A7.02 - VLT is a registered Danfoss trademark
135