Operating instructions

VLT
®
5000 FLUX
Miscellaneous
Warning word 1, Extended status word
and Alarm word
Warning word 1, extended status word and alarm
word are shown on the display in Hex format. If
there are more than one warning or alarm, a sum
of all warnings or alarms will be shown.
Warning word 1, extended status word and alarm
word can also be displayed using the serial bus
in parameter 540, 541 and 538.
Bit (Hex) Warning word 1 (parameter 540)
000001 Fault during brake test
000002 EE-prom power card fault
000004 EE-prom control card
000008 HPFP bus timeout
000010 Standard bus timeout
000020 Overcurrent
000040 Torque limit
000080 Motor thermistor
000100 Motor overload
000200 Inverter overload
000400 Undervoltage
000800 Overvoltage
001000 Voltage warning low
002000 Voltage warning high
004000 Phase fault
008000 No motor
010000 Live zero fault
(4-20 mA current signal low)
020000 10 Volts low
040000 Brake resistor power 100%
080000 Brake resistor fault
100000 Brake transistor fault
200000 Out of frequency range
400000 Fieldbus communication fault
800000 Encoder loss
1000000 Mains failure
2000000 Motor too small
4000000 Motor too big
8000000 CheckP.103andP.105
10000000 CheckP.104andP.106
20000000 Application high
40000000 Application low
80000000 Warning word 2
Bit (Hex) Extended status word (parameter
541)
000001 Ramping
000002 Automatic motor adaptation
000004 Start clockwise/anti-clockwise
000008 Slow down
000010 Catch-up
000020 Feedback high
000040 Feedback low
000080 Output current high
000100 Output current low
000200 Output speed high
000400 Output speed low
000800 Brake test ok
001000 Braking max.
002000 Braking
008000 Out of speed range
010000 Over voltage control active
MG.55.A7.02 - VLT is a registered Danfoss trademark
131