Operating instructions
VLT
®
5000 FLUX
■ Serial communication
■ Introduction
The purpose of the serial communication parameters is to select and adjust parameters in conjunction with
RS 485 field bus. See wiring diagram ’Bus connection’ in the installation section.
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
500 A
Address
1 1 - 126 Yes No 0 6
501 B
Baudrate
9600 Baud Yes No 0 5
502 C
Coasting
Logic or Yes Yes 0 5
503 Q
Quick-stop
Logic or Yes Yes 0 5
504 D
DC-brake
Logic or Yes Yes 0 5
505 S
Start
Logic or Yes Yes 0 5
506 R
Reversing
Digital input Yes Yes 0 5
507 S
Selection of setup
Logic or Yes Yes 0 5
508 S
Selection of speed
Logic or Yes Yes 0 5
509 B
Bus jog 1
200 rpm 0.0 - parameter 202 Yes Yes -1 6
510 B
Bus jog 2
200 rpm 0.0 - parameter 202 Yes Yes -1 6
512 T
Telegram profile
FC Drive No Yes 0 5
513 B
Bus time interval
1 sec. 1 - 99 s Yes Yes 0 5
514 B
Bus time interval function
Off Yes Yes 0 5
515 D
Data read-out: Reference %
No No -1 3
516 D
Data read-out: Reference unit
No No -3 4
518 D
Data read-out: Frequency
No No -1 6
520 D
Data read-out: Current
No No -2 7
521 D
Data read-out: Torque
No No -1 3
522 D
Data read-out: Power, kW
No No -1 7
523 D
Data read-out: Power, HP
No No -2 7
524 D
Data read-out: Motor voltage
No No -1 6
525 D
Data read-out: DC link voltage
No No 0 6
526 D
Data read-out: Motor temp.
No No 0 5
527 D
Data read-out: VLT temp.
No No 0 5
528 D
Data read-out: Digital input
No No 0 5
529 D
Data read-out: Terminal 53,
analogue input
No No -2 3
530 D
Data read-out: Terminal 54,
analogue input
No No -2 3
531 D
Data read-out: Terminal 60,
analogue input
No No -5 3
532 D
Data read-out: Pulse reference
No No -1 7
533 D
Data read-out: External reference %
No No -1 3
534 D
Data read-out: Status word, binary
No No 0 6
535 D
Data read-out: Brake power/2 min.
No No 2 6
536 D
Data read-out: Brake power/sec.
No No 2 6
537 D
Data read-out: Heat sink temperature
No No 0 5
538 D
Data read-out: Alarm word, binary
No No 0 7
539 D
Data read-out: VLT control word, binary
No No 0 6
540 D
Data read-out: Warning word, 1
No No 0 7
541 D
Data read-out: Extended status word
No No 0 7
557 D
Data read-out: Motor RPM
No No 0 4
558 D
Data read-out: Motor RPM x scaling
No No -2 4
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A7.02 - VLT is a registered Danfoss trademark
110