Technical data

Example - Status word and current output frequency:
The master receives a status message from the fre-
quency converter that the current output frequency is
50% of the output frequency range.
Par. 201 Output frequency low limit = 0 Hz
Par. 202 Output frequency high limit = 50 Hz
Status word = 0F03 Hex.
Output frequency = 2000 Hex • 50% of the frequency
range, corresponding to 25 Hz.
VLT
®
2800 Series
MG.27.E3.02 - VLT
®
is a registered Danfoss trademark 125