Technical data

VLT
®
2800 Series
Programming
Description of choice:
Set the output voltage (U1) that is to match the first
output frequency (F1), parameter 424 F1 frequency.
424 F1 frequency
(F1 FREQUENCY)
Value:
0.0 - par. 426 F2 frequenc y
Par. 104 Motor frequency
Function:
See parameter 423 U1 voltage .
Description of choice:
Set the output frequency (F1) that is to match the first
output voltage (U1), parameter 423 U1 voltage .
425 U2 voltage
(U2 VOLTAGE)
Value:
0.0 - 999.0 V
par. 103
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output voltage (U2) that is to match the second
output frequency (F2), parameter 426 F2 frequency.
426 F2 frequency
(F2 FREQUENCY)
Value:
Par. 424 F1 frequency - par. 428 F3 frequency
Par. 104 Motor frequency
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output frequency (F2) that is to match the
second output voltage (U2), parameter 425 U2 voltage .
427 U3 voltage
(U3 VOLTAGE)
Value:
0.0 - 999.0 V
par. 103
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output voltage (U3) that is to match the third
output frequency (F3), parameter 428 F3 frequency .
428 F3 frequency
(F3 FREQUENCY)
Value:
Par. 426 F2 frequenc y - 1000 Hz
Par. 104 Motor frequency
Function:
See parameter 423 U1 voltage.
Description of choice:
Set the output frequency (F3) that is to match the third
output voltage (U3), parameter 427 U3 voltage .
NB!:
Parameters 437-444 are only used
if in parameter 100 Configuration a
selection has been made of Process
regulation, closed loop. [3].
437 Process PID normal/inverse control
(PROC NO/INV CTRL)
Value:
Normal (NORMAL)
[0]
Inverse (INVERSE)
[1]
Function:
It is possible to choose whether the process regulator
is to increase/reduce the output frequency if there
is a deviation between the reference/setpoint
and the actual process mode.
Description of choice:
If the frequency converter is to reduce
the output frequency in case the feed-
back signal increases, select Normal [0].
If the frequency converter is to increase the
output frequency in case the feedback signal
increases, select Inverse [1].
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A9.02 - VLT is a registered Danfoss trademark