User guide
Profinet IO vacon • 29
24-hour support +358 (0)40 837 1150 • Email: fieldbus@vacon.com
1
5.1.4.
Reference
This is the reference 1 to the frequency converter. Used normally as Speed reference.
The allowed scaling is –10000...10000. In the application, the value is scaled in percentage of the fre-
quency area between set minimum and maximum frequency.
-10000 = 100,00 % (Direction reverse)
0 = 0,00 % (Direction forward)
10000 = 100,00 % (Direction forward)
5.1.5.
Actual value
This is the actual value from the frequency converter. Value between -10000...10000. In the applica-
tion, the value is scaled in percentage of frequency area between set minimum and maximum fre-
quency.
-10000 = 100,00 % (Direction reverse)
0 = 0,00 % (Direction forward)
10000 = 100,00 % (Direction forward)
5.1.6.
Process data in
ProcessData Master -> Slave
The Master can write max. 8 additional setting values to the device with the help of the Process Data.
How these setting values are used is totally dependent on the application in use.
5.1.7.
Process data out
ProcessData Slave -> Master
The master can read the frequency converter’s actual values using the process data variables.
Depending on the used application, the contents are either standard or can be selected with a para-
meter.